Plan Review Notes For Permit 14080234
Permit Number 14080234
Review Stop E
Sequence Number 2
Notes
Date Text
2014-09-22 14:42:25DATE: 9/22/2014
 PROJECT: 36TH ST REAR BLDG
 PERMIT#: 14080234
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 2) PROVIDE A RISER DIAGRAM, AND A PANEL SCHEDULE.
  
 3) IDENTIFY THE LOCATIONS OF THE ELECTRICAL SERVICE AND
 THE ELECTRICAL PANEL. IDENTIFY THE CIRCUITRY OF THE
 OUTLETS AND LIGHTS THROUGHOUT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  