2014-09-13 10:54:39 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. OUR RECORDS DO NOT SHOW A PERMIT FOR THE FIRST FLOOR |
| APARTMENT, REAR STRUCTURE. |
| |
| PLANS ARE NOT CLEAR AS TO SCOPE AND DO NOT MAKE |
| REFERENCE TO A CHANGE OF OCCUPANCY. AS THE TUB WAS |
| SHOWN AS "EXISTING", MY INITIAL REVIEW WAS DONE ON |
| WINDOWS ONLY. PLANS DO NOT SHOW THAT THE ENTIRE FIRST |
| FLOOR IS A GARAGE TO BE CONVERTED TO AN APARTMENT. |
| |
| ANYTHING WHICH WAS BUILT WITHOUT A PERMIT IS NOT |
| "EXISTING." THE ISSUE OF THE REAR BUILDING HAS ALREADY |
| BEEN BROUGHT UP IN THE PAST BY ANOTHER PLANS EXAMINER |
| ON ANOTHER PERMIT. |
| |
| PROVIDE AN "EXISTING" PLAN FOR BOTH FLOORS. "EXISTING" |
| IS TO SHOW CONDITIONS WHICH WERE LEGALLY PERMITTED. |
| |
| PROVIDE A "PROPOSED" PLAN WHICH SHOWS ALL PROPOSED |
| CONSTRUCTION, INCLUDING ITEMS WHICH MAY BE ALREADY |
| INSTALLED BUT WERE CONSTRUCTED WITHOUT A PERMIT. UNLESS |
| PERMITTED, IT IS NOT "GRANDFATHERED" REGARDLESS OF WHEN |
| THE CONSTRUCTION WAS DONE. |
| |
| PLANS ARE TO INCLUDE METHOD OF COMPLIANCE SELECTED, SEE |
| FBC 2010 EXISTING BUILDING 101.5. THIS APPEARS TO BE |
| BOTH AN ALTERATION AS WELL AS A CHANGE OF OCCUPANCY. |
| PLANS SHOULD INCLUDE THIS INFORMATION FOR AN ACCURATE |
| PLAN REVIEW. |
| |
| IT APPEARS THAT THERE IS ONE EXISTING UNIT (2ND FLOOR), |
| AND A NEW APARTMENT IS PROPOSED, BUT NO TENANT |
| SEPARATION WAS SHOWN. ENERGY CALCS WERE NOT PROVIDED. |
| INSULATION, WALL DETAILS, ETC. WERE NOT PROVIDED. |
| |
| A COMPLETE CHECKLIST CANNOT BE PROVIDED AT THIS TIME |
| DUE TO THE AMBIGUITY OF THE PLAN PROVIDED. |
| |