Plan Review Notes For Permit 14080234 |
Permit Number |
14080234 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-22 18:17:43 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING | | INFORMATION FOR THE 38" HIGH BEDROOM WINDOWS; FBC R310, | | FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY | | MORE THAN 5%: | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | MANUFACTURER | | | | |
|