 COMPUTER CABLING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PLANS ARE NOT SUFFICIENTLY DETAILED. NEC 110.3, 110.8,
 110.11, 110.12, 300-5, 300.21, 300.22, 800.18, 800.24,
 800.25, 800.26, 800.47
  
  
  
 PROVIDE SPECIFICATIONS ON CABLE.
 INDICATE LOCATION AND PURPOSE OF ALL DROPS.
 VERIFY THAT CABLES LOCATED AT OR BELOW GRADE ARE
 SUITABLE FOR WET LOCATIONS.
 VERIFY THAT CABLES ARE PLENUM RATED IF LOCATED IN
 ENVIRONMENTAL AIR HANDLING SPACES.
 INDICATED HOW CABLE WILL BE PROTECTED AND SUPPORTED.
 PLANS NEED TO BE SIGNED AND DATED BY THE CONTRACTOR
 PROVIDE A FIRE STOPPING DETAIL FOR ANY PENETRATIONS FOR
 FIRE RATED ASSEMBLIES.
  
  