2014-08-12 12:43:52 | 14080199 | | 854 CONNISTON RD | | COMPUTER CABLING | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PLANS ARE NOT SUFFICIENTLY DETAILED. NEC 110.3, 110.8, | | 110.11, 110.12, 300-5, 300.21, 300.22, 800.18, 800.24, | | 800.25, 800.26, 800.47 | | | | | | | | PROVIDE SPECIFICATIONS ON CABLE. | | INDICATE LOCATION AND PURPOSE OF ALL DROPS. | | VERIFY THAT CABLES LOCATED AT OR BELOW GRADE ARE | | SUITABLE FOR WET LOCATIONS. | | VERIFY THAT CABLES ARE PLENUM RATED IF LOCATED IN | | ENVIRONMENTAL AIR HANDLING SPACES. | | INDICATED HOW CABLE WILL BE PROTECTED AND SUPPORTED. | | PLANS NEED TO BE SIGNED AND DATED BY THE CONTRACTOR | | PROVIDE A FIRE STOPPING DETAIL FOR ANY PENETRATIONS FOR | | FIRE RATED ASSEMBLIES. | | | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | 561-805-6700 | | | | | | |
|