Plan Review Notes
Plan Review Notes For Permit 14080111
Permit Number 14080111
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-04 17:55:482010 FBC
  
 DENIED BY BUILDING
  
 1) THE MEAN ROOF HEIGHT (MRH) IS SPECIFIED AS 12' ON
 THE RAS 117 CALCULATIONS AND 30' ON THE APPLICATION.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1 AND FBCR
 301.2.1
  
 2) THE DESIGN WIND PRESSURES ARE INCORRECT FOR 170 MPH
 (132 MPH VASD) EXPOSURE C WITH A 30' MRH AND A 0 TO 7
 DEGREE ROOF SLOPE. THE UPLIFT PRESSURES ARE -43.8 PSF
 FOR ROOF ZONE 1, -73.5 PSF FOR ROOF ZONE 2 AND -110.7
 PSF FOR ROOF ZONE 3. PLEASE CORRECT. FBCR 301.2.1
  
 3) PLEASE REVISE THE FASTENER SPACING CALCULATIONS
 USING THE CORRECTED PRESSURES. CITY AMENDMENTS 107.2.1
 AND FBCR 301.2.1
  
 4) THE VALUATION FOR THE WORK IS TOO LOW FOR A 5,300
 SQFT MODIFIED BITUMEN ROOF SYSTEM. BASED ON THE
 MARSHALL AND SWIFT VALUATION GUIDE, THE AVERAGE
 VALUATION IS $5.30 PER SQUARE FOOT. BASED ON THIS, THE
 VALUATION FOR THIS PROJECT IS $28,090.00 AND WILL BE
 ADJUSTED ACCORDINGLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]