2014-08-08 16:16:25 | BUILDING PLAN REVIEW |
| PERMIT: 14080109 |
| ADD: 1045 CHARLOTTE |
| CONT: THE CARPENTER'S SON |
| TEL: ()452-2191 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRIDAY AUG. 08/2014 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLAN IS A STATE APPROVED PLANS FOR A |
| RESIDENTIAL STORAGE SHED (BUILDING CATEGORY I) , 180 |
| VALT / EXP. D, PLEASE REVIEW ISSUES AT HAND: |
| 1A) THE OCCUPANCY CLASSIFICATION IS BEING CHANGED TO A |
| BUSINESS OCCUPANCY, A GUARD SHACK, THE BUILDING |
| CATEGORY II HAS CHANGED, THIS WILL INCREASE THE |
| REQUIRED PRESSURES. |
| 1B) WITH THE OCCUPANCY CHANGE REQUIRING THE BUILDING TO |
| BE A BUILDING CATEGORY LL THIS MAY AFFECT THE ANCHORING |
| OF THE STRUCTURE, THE ANCHORING ENGINEERING WILL ALSO |
| NEED TO BE REVIEWED. |
| 1C) PLEASE NOTE ALSO THE REQUIREMENT FOR COMPONENTS AND |
| CLADDING WINDOWS AND DOORS WILL NEED TO HAVE EITHER |
| LARGE MISSILE IMPACT GLAZING OR STORM SHUTTERS. 2010 |
| FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| 1D) THE STATE PLANS SHEET 1 NOTE # 11 INDICATE FOR A |
| RESIDENTIAL USE A ACCESORY SRUCTURE THE DOOR MAY BE 72 |
| INCHES, NOTE # 12 FOR COMMERCIAL USE THE DOOR MUST BE |
| 6'-8" TALL. FBC-B 1008.1.1. |
| 1E) THE STATE APPROVED PLANS DO INDICATE THAT THE NOTE |
| # 4 THE GUTTER SYSTEM IS A SITE INSTALLED SYSTEM AND |
| THE CONTRACTOR WILL NEED TO SUBMIT THE GUTTER AND DOWN |
| SPOUT TO BE INSTALLED. 2010 FBC-B 1503.7 PROTECTION |
| AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| 2) IT WOULD APPEAR THE MANUFACTURER OF THE BUILDING |
| SHOULD MAKE A REVISION TO THE STATE APPROVED PLANS FOR |
| THE BUSINESS USE OCCUPANCY, THEN THE STATE APPROVED |
| PLANS WOULD ADDRESS THE COMMENTS 1A-1D. |
| 1E) GUTTERS WILL STILL BE A SITE INSTALLED BY THE |
| CONTRACTOR. |
| |
| 3) PLEASE IDENTIFY WHICH TYPE OF BUILDING TO BE |
| INSTALLED, GABLE END, HIP OR SHED TYPE ROOF. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |