Plan Review Notes
Plan Review Notes For Permit 14080109
Permit Number 14080109
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-08 16:16:25BUILDING PLAN REVIEW
 PERMIT: 14080109
 ADD: 1045 CHARLOTTE
 CONT: THE CARPENTER'S SON
 TEL: ()452-2191
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUG. 08/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN IS A STATE APPROVED PLANS FOR A
 RESIDENTIAL STORAGE SHED (BUILDING CATEGORY I) , 180
 VALT / EXP. D, PLEASE REVIEW ISSUES AT HAND:
 1A) THE OCCUPANCY CLASSIFICATION IS BEING CHANGED TO A
 BUSINESS OCCUPANCY, A GUARD SHACK, THE BUILDING
 CATEGORY II HAS CHANGED, THIS WILL INCREASE THE
 REQUIRED PRESSURES.
 1B) WITH THE OCCUPANCY CHANGE REQUIRING THE BUILDING TO
 BE A BUILDING CATEGORY LL THIS MAY AFFECT THE ANCHORING
 OF THE STRUCTURE, THE ANCHORING ENGINEERING WILL ALSO
 NEED TO BE REVIEWED.
 1C) PLEASE NOTE ALSO THE REQUIREMENT FOR COMPONENTS AND
 CLADDING WINDOWS AND DOORS WILL NEED TO HAVE EITHER
 LARGE MISSILE IMPACT GLAZING OR STORM SHUTTERS. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 1D) THE STATE PLANS SHEET 1 NOTE # 11 INDICATE FOR A
 RESIDENTIAL USE A ACCESORY SRUCTURE THE DOOR MAY BE 72
 INCHES, NOTE # 12 FOR COMMERCIAL USE THE DOOR MUST BE
 6'-8" TALL. FBC-B 1008.1.1.
 1E) THE STATE APPROVED PLANS DO INDICATE THAT THE NOTE
 # 4 THE GUTTER SYSTEM IS A SITE INSTALLED SYSTEM AND
 THE CONTRACTOR WILL NEED TO SUBMIT THE GUTTER AND DOWN
 SPOUT TO BE INSTALLED. 2010 FBC-B 1503.7 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 2) IT WOULD APPEAR THE MANUFACTURER OF THE BUILDING
 SHOULD MAKE A REVISION TO THE STATE APPROVED PLANS FOR
 THE BUSINESS USE OCCUPANCY, THEN THE STATE APPROVED
 PLANS WOULD ADDRESS THE COMMENTS 1A-1D.
 1E) GUTTERS WILL STILL BE A SITE INSTALLED BY THE
 CONTRACTOR.
  
 3) PLEASE IDENTIFY WHICH TYPE OF BUILDING TO BE
 INSTALLED, GABLE END, HIP OR SHED TYPE ROOF.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  