Notes
Date Text
2014-08-13 11:41:40900 FLORIDA AVENUE - TRAILERS
 PERMIT #14080108
 MASTER #14060484
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO NFPA 24 AND NFPA 13 IN LIEU OF
 THE PROPOSED NFPA 13D SYSTEMS.
  
 PROVIDE WATER SUPPLY/HYDRANT FLOW TEST INFORMATION ON
 THE PLANS.
  
 PROVIDE A SITE PLAN DETAILING TRAILER LOCATIONS, NORTH
 DIRECTION, FIRE HYDRANT LOCATIONS, FDCS, WATER MAIN TAP
 SIZE, ETC.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME.
  
 NO PRODUCT DATA SUBMITTED FOR PIPE, HANGERS, BACKFLOW
 PREVENTION DEVICES, FLOW SWITCHES, ETC.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]