2014-10-02 18:25:53RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C PLAN SUBMITTED IN DRAWING M-1 DOESN'T MATCH
 ARCHITECTURAL PLAN. A/C PLAN SHOWS 14 X 8 PASS-THROUGH
 RETURN, WHILE ARCHITECTURAL PLAN ON SHEET A-1 SHOWS
 R.A.G. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- PERSON RESPONSIBLE FOR THE A/C DESIGN TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 ***NOTE: SEPARATE MECHANICAL PERMIT WILL BE REQUIRED
 AND VALUATION FOR THE MECHANICAL WORK IS NOT INCLUDED
 IN THE MASTER PERMIT APPLICATION
  
  
  