Plan Review Notes For Permit 14080085 |
Permit Number |
14080085 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-02 15:04:56 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | CHECKLIST: | | CODE: 2010 FBC. | | | | 1- GARAGE IS CONVERTED TO BEDROOM (SEE BEDROOM | | DEFINITION IN CHAPTER 2 OF 2010 FBC-ENERGY | | CONSERVATION). PLANS NEED TO PROVIDE SPECIFICATIONS | | SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. | | R310 OF 2010 FBC-RESIDENTIAL. | | REPEAT COMMENT. NEED MEANS OF EGRESS. SEE THE | | DEFINITION OF BEDROOM IN THE 2010 FBC-ENERGY | | CONSERVATION. A ROOM WITH A CLOSET IS CONSIDERED A | | BEDROOM. NO HAVING A DOOR DOESN'T EXEMPT IT FROM BEING | | A BEDROOM. (NOTE: AN STUDIO OR A LOFT DON'T HAVE DOORS | | EITHER). REVISE PLANS AS REQUIRED. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR THE NEW EGRESS WINDOW. | | | | 3- NEW INSULATION NOTE ON SHEET A-1: PROVIDE COMPLETE | | DETAILS AND SPECIFICATIONS SHOWING HOW PROVIDING R-7.8 | | INSULATION ON INSIDE OF EXISTING CMU EXTERIOR WALLS AS | | REQUIRED BY SEC. 103.2.2 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|