2014-08-22 17:30:49 | ****PROVISO**** |
| ****ISSUED AT CONTRACTOR'S RISK**** |
| ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** |
| ****REVISED ON 8/26/14**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC 109, VALUE TO INCLUDE THE VALUE OF LABOR, |
| MATERIALS, OVERHEAD, PROFIT, ENGINEERING/ARCHITECTURE. |
| VALUE OF $850 ON PERMIT APPLICATION IS TOO LOW. PROVIDE |
| A COPY OF THE CONTRACT FOR THIS JOB. VALUE TO BE |
| REASONABLE, OTHERWISE AN ESTIMATE USING MARSHALL & |
| SWIFT WILL BE REQUIRED. |
| |
| ARCHITECT TO REVISE PLAN TO INCLUDE WIND DESIGN |
| CRITERIA, FBC1603.1.4. |
| |
| ARCHITECT TO REVISE PLAN TO INCLUDE FLOOD DESIGN DATA, |
| FBC 1603.1.7. AN ELEVATION CERTIFICATE WILL BE HELPFUL |
| IN DETERMINING DESIGN CRITERIA REQUIRED. THE ELEVATION |
| CERTIFICATE MAY BE SENT VIA EMAIL. |
| |
| DECK ELEVATIONS (DRAWINGS) MAY BE REQUIRED DEPENDING ON |
| INFORMATION ON THE ELEVATION CERTIFICATE. IT IS NOT |
| CLEAR HOW HIGH THE DECK IS, AND WHETHER THERE IS AN |
| ENCLOSURE UNDER THE DECK OR OPEN SPACE. COMPLIANCE WITH |
| NFIP REGULATIONS (FLOOD/FEMA) AND FBC 1603.1.7 CANNOT |
| BE DETERMINED AT THIS TIME. |
| |
| A MORE COMPLETE PLAN REVIEW WILL BE PROVIDED AFTER |
| RECEIPT OF AN ELEVATION CERTIFICATE. |
| |
| ****NEW COMMENT 8/26/2014**** |
| |
| ADD FLOOR LOAD DESIGN CRITERIA TO THE PLAN (DEAD LOAD |
| AND LIVE LOAD), SEE FBC TABLE 1607.1, FBC 1603.1. |
| |