Plan Review Notes For Permit 14080067 |
Permit Number |
14080067 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-06 09:48:13 | ROOFING ALTERATION, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PER PHONE CONVERSATION WITH MR. TERRENCE MOTTLEY | | (CONTRACTOR), THE SCOPE OF WORK IS TO BUILT A MANSARD | | ON THE FRONT ELEVATION OF THE BUILDING. I TOLD HIM THAT | | HE NEEDS TO PROVIDE COMPLETE SET OF DRAWINGS AND | | SPECIFICATIONS SHOWING THE MANSARD CONSTRUCTION AS | | REQUIRED BY SEC. 1609 FBC. | | | | 2- PROVIDE PRODUCT APPROVALS (2 COPIES AS REQUIRED BY | | DCA RULE 9N-3) FOR ALL STRUCTURAL CONNECTORS SPECIFIED | | BY THE DESIGN PROFESSIONAL. PROVIDE ONLY THE PRODUCT | | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED | | CONNECTORS. | | | | 3- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE | | IN WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. | | 107. 3.4.1 OF CITY AMENDMENTS TO FBC. | | | | 4- UPDATE VALUATION DECLARED IN THE PERMIT APPLICATION | | TO INCLUDE THE MANSARD CONSTRUCTION AND ROOFING PANELS. | | SEC. 109.3 CITY AMENDMENTS TO FBC. | | | | ***NOTE: NEED BUILDING AND ROOFING PERMITS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|