2014-08-26 15:17:28 | DATE: 8/18/2014 |
| PROJECT: CARSON 240 PALMETTO LN |
| PERMIT#: 14080064 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 3RD ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| DUPLICATE COMMENT: |
| 1) NEC 310.15(6) |
| STATES IN PART "FOR APPLICATION OF THIS SECTION, THE |
| MAIN POWER FEEDER SHALL BE THE FEEDER BETWEEN THE MAIN |
| DISCONNECT AND THE PANELBOARD THAT SUPPLIES, EITHER BY |
| BRANCH CIRCUITS OR BY FEEDERS, OR BOTH, ALL LOADS THAT |
| ARE PART OR ASSOCIATED WITH THE DWELLING UNIT. " |
| THIS MEANS ONLY ONE SERVICE ENTRANCE OR FEEDER TO ONE |
| MAIN NOT MORE THAN ONE. THE PURPOSE OF THIS SECTION IS |
| TO DIVERSIFY THE TOTAL LOAD EVENLY ACCROSS THE |
| CONDUCTORS WHEN THERE IS MORE THAN ONE MAIN THAT CAN |
| NOT BE ACCOMPLISHED. THEREFORE A FULL SIZE SERVICE |
| ENTRANCE AND FEEDER IS REQUIRED. SEE NEC310.16 REVISE |
| THE RISER DIAGRAM ACCORDINGLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |