2014-08-26 15:17:28DATE: 8/18/2014
 PROJECT: CARSON 240 PALMETTO LN
 PERMIT#: 14080064
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENT:
 1) NEC 310.15(6)
 STATES IN PART "FOR APPLICATION OF THIS SECTION, THE
 MAIN POWER FEEDER SHALL BE THE FEEDER BETWEEN THE MAIN
 DISCONNECT AND THE PANELBOARD THAT SUPPLIES, EITHER BY
 BRANCH CIRCUITS OR BY FEEDERS, OR BOTH, ALL LOADS THAT
 ARE PART OR ASSOCIATED WITH THE DWELLING UNIT. "
 THIS MEANS ONLY ONE SERVICE ENTRANCE OR FEEDER TO ONE
 MAIN NOT MORE THAN ONE. THE PURPOSE OF THIS SECTION IS
 TO DIVERSIFY THE TOTAL LOAD EVENLY ACCROSS THE
 CONDUCTORS WHEN THERE IS MORE THAN ONE MAIN THAT CAN
 NOT BE ACCOMPLISHED. THEREFORE A FULL SIZE SERVICE
 ENTRANCE AND FEEDER IS REQUIRED. SEE NEC310.16 REVISE
 THE RISER DIAGRAM ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]