2014-08-18 15:51:52DATE: 8/18/2014
 PROJECT: CARSON 240 PALMETTO LN
 PERMIT#: 14080064
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 310.15(6)
 STATES IN PART "FOR APPLICATION OF THIS SECTION, THE
 MAIN POWER FEEDER SHALL BE THE FEEDER BETWEEN THE MAIN
 DISCONNECT AND THE PANELBOARD THAT SUPPLIES, EITHER BY
 BRANCH CIRCUITS OR BY FEEDERS, OR BOTH, ALL LOADS THAT
 ARE PART OR ASSOCIATED WITH THE DWELLING UNIT. "
 THIS MEANS ONLY ONE SERVICE ENTRANCE OR FEEDER TO ONE
 MAIN NOT MORE THAN ONE. THE PURPOSE OF THIS SECTION IS
 TO DIVERSIFY THE TOTAL LOAD EVENLY ACCROSS THE
 CONDUCTORS WHEN THERE IS MORE THAN ONE MAIN THAT CAN
 NOT BE ACCOMPLISHED. THEREFORE A FULL SIZE SERVICE
 ENTRANCE AND FEEDER IS REQUIRED. REVISE THE RISER
 DIAGRAM ACCORDINGLY.
  
 2) THE SCOPE OF WORK REFERRED TO AT THE TOP OF THE
 RISER DIAGRAM IS NOT REFLECTED ACURATELY IN THE PLAN
 SUBMITTED. EXAMPLE: IT IS STATED IN THE SCOPE OF WORK
 THAT THE 20KW GENERATOR AND 100AMP ATS WILL BE REAPLCED
 WITH A 48 KW GENERATOR AND A 400AMP ATS. HOWEVER THE
 RISER DIAGRAM ILLUSTRATES THE USE OF TWO 200AMP ATS'S
 NOT ONE 40AMP ATS. CLARIFICATION REQUIRED.
  
 3) THE GROUNDING ELECTRODE CONDUCTOR ILLUSTRATED ON THE
 PLAN INDICATES THE USE OF A #3CU CONDUCTOR. NEC 250.66
 IS THE SECTION USED FOR THIS SELECTION. IN THIS ARTICLE
 IT STATES IN ORDER TO DETERMINE THE CORRECT SIZE OF
 CONDUCTOR FOR USE AS A GROUDING ELECTRODE CONDUCTOR YOU
 NEED TO KNOW THE SIZE OF THE SERVICE ENTRANCE
 CONDUSTOR. THE SERVICE ENTRANCE CONDUCTOR IS NOT
 ILLUSTRATED OR INDICATED ON THE PLANS SUBMITTED. REVISE
 THE RISER DIGRAM TO INDICATE THE SIZE OF THE SERVICE
 ENTRANCE CONDUCTORS.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
 PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DEIGN. SEE FBC 107.2.1 ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,