2014-08-04 09:51:04DATE: 8/4/2014
 PROJECT: DONAL CARSON
 PERMIT#: 14080064
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 702.5 CAPACITY AND RATING.
 (A) AVAILABLE SHORT-CIRCUIT CURRENT. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 AVAILABLE SHORT-CIRCUIT CURRENT AT ITS TERMINALS.
 THEREFORE: PROVIDE AIC CALCULATIONS.
  
 (B) SYSTEM CAPACITY. THE CALCULATIONS OF LOAD ON THE
 STANDBY SOURCE SHALL BE MADE IN ACCORDANCE WITH ARTICLE
 220 OR BY ANOTHER APPROVED METHOD. THEREFORE: PROVIDE
 LOAD CALCULATION.
  
 2) REVISE THE RISER DIAGRAM TO INCLUDE THE GROUNDING
 ELECTRODE SYSTEM. INCLUDE ELECTRODE TYPES AND LOCATIONS
 ALONG WITH WIRE SIZES AND TERMINATIONS. NEC 250.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 PLEASE INSERT CORRECTED PAGES INTO SUBMITTAL PACKAGE
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  