2014-12-15 11:46:02 | 12/15/2014 | | PROJECT: AUTOZONE #4938 | | PERMIT#: 14080059 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) VERIFY THAT THE INTERIOR AND EXTERIOR LIGHTING | | CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE | | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL | | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME | | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST | | 10 HOURS. FBC ENERGY CONSERVATION 505.2 | | | | 2) VERIFY SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | DISCONNECTING MEANS. NEC 110.16, 110.22 | | | | 3) VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL | | BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT | | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT | | CURRENT AT THE SERVICE POINT OF THE ELECTRICAL UTILITY. | | NEC 110.9, 110.10 | | | | 4) VERIFY DIMENSIONS AND LISTING FOR THE ELECTRICAL | | SERVICE WIREWAY. NEC 110-26, 314.28 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | | | | | |
|