2014-11-22 11:22:28 | BUILDING PLAN REVIEW |
| PERMIT: 14080059 |
| ADD: 5660 N MILITARY TRL. |
| CONT: TBD |
| TEL: (901)495-8701 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| NOTE: PLANS WERE SUBMITTED BY MAIL "NO PERMIT |
| APPLICATION WAS PROVIDED", SUBMITTED AS A TBD" TO BE |
| DETERMINED" BEFORE PERMIT ISSUANCE A QUALIFIED |
| CONTRACTOR WILL NEED TO SUBMIT A SIGNED AND NOTIRIZED |
| PERMIT APPLICATION BY THE OWNER AS WELL AS THE |
| CONTRACTOR. |
| |
| 2ND REVIEW |
| DATE: SAT. NOV. 22/2014 |
| ACTION: DENIED |
| |
| |
| NOTICE:!!!!!!!!!!!!!!!! |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| |
| 1)COMPLIED. SITE PLAN. |
| |
| 2) 2ND REQUEST. THE SUBMITTED SOILS REPORTS ARE COPIES |
| OF ORIGINAL SOILS REPORTS. THE REPORT HAS A COPIED |
| ENGINEERS SIGNATURE, & NO SEAL. |
| |
| 61G15-23.002(1) SEAL, SIGNATURE AND DATE SHALL BE |
| AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME |
| AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, |
| REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR |
| THE OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED |
| OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| |
| MISSING SOILS REPORT 2010 FBC-B 1803.2 INVESTIGATIONS |
| REQUIRED. GEOTECHNICAL INVESTIGATIONS SHALL BE |
| CONDUCTED IN ACCORDANCE WITH SECTIONS 1803.3 THROUGH |
| 1803.5. |
| 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION |
| SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS |
| OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR |
| OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE |
| LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS |
| NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, |
| POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT |
| OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, |
| COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS. |
| |
| 3) PARTIAL APPROVED. THE DESIGNER OF RECORD HAS |
| REQUESTED THE MISSING PRODUCT APPROVALS TO COME IN |
| AFTER PERMIT ISSUANCE AS DEFERRED SUBMITTALS. THE |
| COVERSHEET A0 LIST THE PRODUCT APPROVALS, WE REQUIRE |
| THE PRODUCT APPROVALS 2 COPIES OF EACH ON E FOR RECORD |
| RETENION THE OTHER FOR THE FIELD INSPECTORS. |
| WINDOWS AND DOORS WITH GLAZING, IDENTIFY WHICH MODEL IF |
| MORETHAN ONE TYPE IS LISTED (FL REPORTS), IDENTIFY THE |
| TYPE OF GLAZING TO BE INSTALLED, INDENTIFY WIDTH & |
| LENGTH OF GLAZING UNITS, MULLIONS, AND ASSOCIATED |
| PRESSURES. ETC. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. MISSING YKK FL 16554-R2 |
| (B) WINDOWS FIXED FL. 16314-R1 / STOREFRONT FL 14218-R2 |
| (D) ROOFING PRODUCTS AND ASSEMBLIES GAF NOA 12-1218.04 |
| TO BE SUBMITTED AS A DERRED SUBMITTAL |
| |
| 4) DEFERRED SUBMITTALS. 2010 FBC 107.3.4.1 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 5) DEFERRED SUBMITTAL: 107.2.1.2 FOR ROOF ASSEMBLIES |
| REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| |
| 6) DEFERRED SUBMITTAL. PLEASE PROVIDE THE EFIS |
| MANUAFACTURERS SPECIFICATIONS FOR INSTALATION. 107.2.4 |
| EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL |
| BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN |
| SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH THIS |
| CODE. THE CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS |
| OF THE EXTERIOR WALL ENVELOPE AS REQUIRED, INCLUDING |
| FLASHING, INTERSECTIONS WITH DISSIMILAR MATERIALS, |
| CORNERS, END DETAILS, CONTROL JOINTS, INTERSECTIONS AT |
| ROOF, EAVES OR PARAPETS, MEANS OF DRAINAGE, |
| WATER-RESISTIVE MEMBRANE AND DETAILS AROUND OPENINGS. |
| THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING |
| DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING |
| DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS |
| MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL |
| ENVELOPE. THE SUPPORTING DOCUMENTATION SHALL FULLY |
| DESCRIBE THE WALL SYSTEM WHICH WAS TESTED, WHERE |
| APPLICABLE, AS WELL AS THE TEST PROCEDURE USED. |
| |
| 7) DEFERRED SUBMITTAL. SHEET A3 DETAIL # 1 AS WELL AS |
| THE ENERGY CALCS INDICATE THE USE OF R-30 INSULATION, |
| PLEASE PROVIDE A CROSS SECTION OF ROOF WITH THE THE |
| R-30 INSULATION, THE TYPE OF MATERIAIL ANAD HOW IT WILL |
| BE ATTACHED TO THE ROOF DECK. ENERGY CODE WHOLE |
| BUILDING METHOD 506.3.1./ COMPONENTS & CLADDING |
| 1609.1.2. |
| |
| 8) COMPLIED. SHEET S2 DETAIL #4. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) COMPLIED. P. B. C. IMPACT FEE ASSESSMANT. |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |