2014-08-30 09:02:232010 WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHT. A-4-THE GUARDRAILS AT THE DRINKING FOUNTAINS
 SHALL NOT IMPINGE ON THE REQUIRED CLEAR FLOOR SPACE FOR
 THE FIXTURE. THE REQUIRED 30" X 48" CLEAR FLOOR SPACE
 SHALL BE CENTERED ON THE FIXTURE PER THE 2010 FAC
 SEC.602.2.. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE
 FLOOR PLAN.
 2) SHT. A-4- DETIAL #6 (INTERIOR BATHROOM ELEVATIONS)
 ACCESSORY #7- A VERTICALLY MOUNTED GRAB BAR IS SHOWN.
 THIS IS NOT PERMITTED PER THE FAC SEC.609.4.
 3) SHT.A-4-DETAIL #4- THE TOILET PAPER DISPENSER SHALL
 BE LOCATED 9 INCHES MAXIMUMTO THE CENTER LINE OF THE
 DISPENSER PER SEC. 604.7 OF THE 2010 FAC.
 4) SHT. M-2- THE HOT AND COLD WATER LINES ARE REVERSED
 AT THE LAVS ON THE WATER RISER. THE HOT WATER SHALL BE
 ON THE LEFT SIDE PER THE 2010 FPC SEC.607.4.
 5)A SEPARATE SHUTOFF VALVE IS REQD. FOR THE ROOFTOP
 HOSE BIBB PER THE 2010 FPC SEC.606.2.(2).
 6) A CLEANOUT IS REQD. IN THE BASE OF THE STACK FOR THE
 MOP SINK PER 2010 FPC SEC.708.3.4.
 REVIEWED BY:
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  