Plan Review Notes For Permit 14080059 |
Permit Number |
14080059 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-30 09:02:23 | 2010 WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. | | 1) SHT. A-4-THE GUARDRAILS AT THE DRINKING FOUNTAINS | | SHALL NOT IMPINGE ON THE REQUIRED CLEAR FLOOR SPACE FOR | | THE FIXTURE. THE REQUIRED 30" X 48" CLEAR FLOOR SPACE | | SHALL BE CENTERED ON THE FIXTURE PER THE 2010 FAC | | SEC.602.2.. SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE | | FLOOR PLAN. | | 2) SHT. A-4- DETIAL #6 (INTERIOR BATHROOM ELEVATIONS) | | ACCESSORY #7- A VERTICALLY MOUNTED GRAB BAR IS SHOWN. | | THIS IS NOT PERMITTED PER THE FAC SEC.609.4. | | 3) SHT.A-4-DETAIL #4- THE TOILET PAPER DISPENSER SHALL | | BE LOCATED 9 INCHES MAXIMUMTO THE CENTER LINE OF THE | | DISPENSER PER SEC. 604.7 OF THE 2010 FAC. | | 4) SHT. M-2- THE HOT AND COLD WATER LINES ARE REVERSED | | AT THE LAVS ON THE WATER RISER. THE HOT WATER SHALL BE | | ON THE LEFT SIDE PER THE 2010 FPC SEC.607.4. | | 5)A SEPARATE SHUTOFF VALVE IS REQD. FOR THE ROOFTOP | | HOSE BIBB PER THE 2010 FPC SEC.606.2.(2). | | 6) A CLEANOUT IS REQD. IN THE BASE OF THE STACK FOR THE | | MOP SINK PER 2010 FPC SEC.708.3.4. | | REVIEWED BY: | | TIM LARGE- | | CHIEF PLUMBING INSPECTOR | | TEL:561-805-6692 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|