 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 SHOW THE PROPOSED LOCATION OF THE ELECTRICAL SERVICE.
 VERIFY SAFE WORKING CLEARANCE HAS BEEN PROVIDED AT THE
 SERVICE, PANEL BOARDS AND DISCONNECTS. NEC 110.26,
 240.24(D)
  
 VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT
 CURRENT AT THE SERVICE POINT OF THE ELECTRICAL UTILITY.
 NEC 110.9, 110.10
  
 PROVIDE DIMENSIONS AND LISTING FOR THE ELECTRICAL
 SERVICE WIREWAY. NEC 110-26, 314.28
  
 THE ELECTRIC WATER COOLER REQUIRES GFCI PROTECTION. NEC
 422.52
  
 THE DRINK MACHINE REQUIRES GFCI PROTECTION. NEC 422.51
  
  
 NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE
 ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE
 LIGHTING, SIGNS AND DATA SYSTEMS
  
  