Plan Review Notes
Plan Review Notes For Permit 14080047
Permit Number 14080047
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-05 17:24:51RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- METAL ROOF PRODUCT APPROVAL FL 11651.16 SUBMITTED
 DOESN'T' T MEET THE DESIGN PRESSURES FOR ROOF ZONE #3
 AS REQUIRED BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
 NEED PRODUCT APPROVAL (DCA RULE 9N-3) THAT MEETS THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, INCLUDING ROOF
 ZONE #3.
  
 2- UNDERLAYMENT NOA 11-0705.04 SUBMITTED WAS CLOSED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA OR FLORIDA
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT.
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved