Plan Review Notes For Permit 14080047 |
Permit Number |
14080047 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-05 17:24:51 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- METAL ROOF PRODUCT APPROVAL FL 11651.16 SUBMITTED | | DOESN'T' T MEET THE DESIGN PRESSURES FOR ROOF ZONE #3 | | AS REQUIRED BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL. | | NEED PRODUCT APPROVAL (DCA RULE 9N-3) THAT MEETS THE | | DESIGN PRESSURES FOR ALL ROOF ZONES, INCLUDING ROOF | | ZONE #3. | | | | 2- UNDERLAYMENT NOA 11-0705.04 SUBMITTED WAS CLOSED BY | | MIAMI-DADE. NEED TO PROVIDE CURRENT NOA OR FLORIDA | | PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT. | | (561)805-6712 | | [email protected] |
|