2014-08-02 15:39:21DATE: 8/2/2014
 PROJECT: VICTORIA CIRCLE
 PERMIT#: 14071194
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 408.36(D) BACK-FED DEVICES. PLUG-IN-TYPE
 OVERCURRENT PROTECTION DEVICES OR PLUG-IN TYPE MAIN LUG
 ASSEMBLIES THAT ARE BACK-FED AND USED TO TERMINATE
 FIELD-INSTALLED UNGROUNDED SUPPLY CONDUCTORS SHALL BE
 SECURED IN PLACE BY AN ADDITIONAL FASTENER THAT
 REQUIRES OTHER THAN A PULL TO RELEASE THE DEVICE FROM
 THE MOUNTING MEANS ON THE PANEL. PROVIDE AND INDICATE
 ON THE PLANS THE MANUFACTURER COMPLIANT DEVICE TO BE
 USED WITH THE BACK-FED MAIN BREAKER
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.
 SIGN THE PLANS.
  
 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4 IDENTIFY THE PHOTOCELL AS THE LIGHTING
 CONTROLLER FOR CODE COMPLIANCE.
  
 4) PROVIDE A FIXTURE SCHEDULE AND A COPY OF THE FIXTURE
 PROPOSED TO BE USED FOR THE MOMUMENT WALL SIGN AND A
 DETAIL OF THE INSTALLATION METHOD TO INDICATE
 COMPLIANCE WITH NEC 110.3 AND FBC 107.2.1
  
 ADDITIONAL PERMITS AND SHOP DRAWINGS REQUIRED FOR THE
 INSTALLATION OF THE MONUMENT SIGNS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  