2014-07-31 13:31:1914071169
 7515 S. FLAGLER DRIVE
 RESIDENTIAL TENNIS COURT LIGHTING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 A LIGHTING BRANCH CIRCUIT IS LIMITED TO 15 AND 20 AMPS
 FOR RESIDENTIAL APPLICATIONS. NEC 210.23
  
 PROVIDE SPECIFICATIONS ON LIGHT POLES AND FOOTINGS.
 SHOW HEIGHT AND WIND LOADING INCLUDING EPA FOR THE
 LIGHT POLE AND FIXTURES. FBC 1609.1
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  