2014-08-01 16:31:03 | DATE: 8/1/2014 |
| PROJECT: |
| PERMIT#: |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) ADDITIONAL INFORMATION REQUIRED. IF CORRECT |
| ATTACHMENT OF FIXTURES IS THE INTENT OF THE PERMIT |
| PROVIDE ATTACHMENT DETAILS. THE APPLICATION ALSO |
| INDICATES INSTALLATION OF EXTERIOR LIGHTING TO BUILDING |
| AND WIRING. DETAILS SUCH AS CIRCUITRY, WIRING MEATHODS |
| ROUTING OF CONDUITS, PANEL SCHEDULES, LOAD CALCULATIONS |
| INDICATING THE ADDITIONAL LOAD WITH THE INSTLALLATION |
| OF THE NEW FIXTURES. IF ALL THESE FIXTURES WERE |
| INSTALLED UNDER A SEPARATE PERMIT. PLEASE PROVIDE THAT |
| PERMIT NUMBER SO THE DETAILS OF THE INSTALLATION CAN BE |
| REFERENCED FROM THE PREVIOUS PERMIT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |