2014-11-02 08:05:23 | 1) SHT.A-0.0 - BUILDING CODE BLOCK - YOU HAVE NOW |
| CLASSIFIED THE STRUCTURE AS A "MIXED OCCUPANCY". THERE |
| IS NO SUCH GENERAL CLASSIFICATION IN CHAPTER 3 OF THE |
| FBC. THE DIFFERENT TYPES OF OCCUPANCIES MUST BE |
| LISTED.MY PREVIOUS COMMENT ASKED TO CLARIFY AS TO HOW |
| THE BUILDING COULD BE CLASSIFIED AS ONE TYPE OF |
| OCCUPANCY WHEN IT WAS ACTUALLY A MIXED OCCUPANCY OF |
| SEVERAL CLASSIFICATIONS. I DID NOT REQUEST THAT THE |
| OCCUPANCY BE CHANGED, ONLY TO CLARIFY THE |
| CLASSIFICATION THAT YOU PLACED ON THE STRUCTURE. IF YOU |
| WOULD HAVE NOTED ON THE PREVIOUS SET THAT IT WAS THE |
| MOST RESTRICTIVE I WOULD NOT HAVE RAISED THE QUESTION. |
| 2) 2ND REQUEST - SUBMIT A GAS RISER DIAGRAM FOR |
| REVIEW.SHOW THE TYPE OF PIPING MATERIAL, LENGTHS OF |
| EACH PIPE SECTION, BTU LOAD OF EACH APPLIANCE & TOTAL |
| BTU LOAD ON THE SYSTEM, COMBUSTION AIR REQUIREMENTS, |
| VENTING, LOCATION OF VALVES, REGULATORS, ETC. OR PLACE |
| A NOTE ON BOTH SETS OF PLANS THAT GAS SHALL BE UNDER A |
| SEPARATE PERMIT. |
| 3) 2ND REQUEST - SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS FOR ALL GAS EQUIPMENT & APPLIANCES. APPLIANCES |
| SHALL BE LISTED AND LABELED PER THE 2010 FGC SEC.301.3. |
| 4) THE REQUIRED CLEARANCE AROUNFD A WATER CLOSET SHALL |
| BE A MINIMUM OF 60 INCHES MEASURED PERPENDICULAR FROM |
| THE SIDE WALL AND 56 INCHES MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL. YOU HAVE A DIMENSION |
| OF 5 FT. BY 4FT-6 INCHES WHICH DOES NOT COMPLY. REFER |
| TO THE THE 2010 FL. ACCESS. CODE SEC. 604.3. YOU ONLY |
| NEED TO SHOW THESE DIMENSIONS ONCE ON THE ENLARGED |
| TOILET ROOM PLAN ON SHT.A-1.2. |
| 5) THE GREASE TRAP SHALL BE CONSTRUCTED IN ACCORDANCE |
| WITH THE 2010 FPC SEC.1003.3.4. 2ND REQUEST. SUBMIT |
| DETAILS. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |