2014-11-21 15:22:29BUILDING PLAN REVIEW
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. NOV.21/2014
 ACTION: DENIED
  
 1A) COMPLIED WITH CORRECTED ADDRESS.
  
 1B) COMPLIED.
  
 2) COMPLIED. NEW SITE PLAN.
  
 3) COMPLIED. 3 ORIGINAL SOILS REPORTS.
  
 4) 2ND REQUEST. COVERSHEET: THE BUILDING CODE ANALYSIS
 INDICATES THIS BUILDING TO BE A FIRE SPRINKLERED
 BUILDING. 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.:107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.5
 . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS. THE DESIGNER OF RECORD HAS TAKEN AREA
 INCREASES WITH THE INSTALLATION OF A NFPA 13 SYSTEM,
 2010 FBC-B 504.2., 903.2.1.2 AND 903.2.1.3.
  
 5) COMPLIED. FITNESS CENTER WITH EQUIPMENT LAYOUT.
  
 6) SHEET A-1.0:
 6A) COMPLIED. FIRE BOX SIZING.
  
 6B) 2ND REQUEST. THE THEATER SEATING SHOW RAISED
 SEATING, THE S6 SHEET SHOWS GEO FOAM NO MANUFACTURERS
 SPECS WERE SUBMITTED NOR DOES THE PLANS INDICATE THE
 END OF THE FOAM ARE ENCAPSULATED BY CONCRETE ON THE
 SIDES. FBC-B 2603.4.1.1. THE STRUCTURAL ENGINEER HAS
 SHOWN ON SHEET S-6 THE FOAM BEING TOTALLY ENCLOSED. THE
 CONTRACTOR HAS NOT SUBMITTED PRODUCT TESTING REPORTS
 AND MANUFACTURERS SPECS FOR THE STRUCTURAL FOAM, NOR
 HAS IT BEEN REVIEWED BY THE ENGINEER OF RECORD FOR
 APPROVAL, BY SHOP DRAWING STAMP, APPROVED OR APPROVED
 WITH COMMENT.
  
 7) COMPLIED. 12/02/14
 . THE CONTRACTOR HAS NOT SUBMITTED THE MANUFACTURERS
 SPEC AND REPORT WHERE THIS PRODUCT CAN BE USED AND
 LIMITATIONS OF SAID PRODUCT.
 SHEET A4.1 INDICATES THE USE OF ICYNENE INSULATION AS
 WELL AS THE COVER SHEET ALSO HAS NOTES FOR ICYNENE.
 ICYNENE IS TO BE INSTALLED UNDER THE ROOF DECK. PLEASE
 SUBMIT THE FULL ICYNENE REPORT LISTED ERS 1826 FOR
 REVIEW; 2010 FBC-B 2603.4.1.6. PLEASE PROVIDE WHICH
 AREAS ARE GOING TO HAVE ICYNENE TYPE INSULATION AND
 WHICH AREAS OF THE ROOFING ARE GOING TO HAVE ROOF TOP
 INSULATION ON TOP OF THE ROOF DECK AS DEPICTED IN
 DETAILS B-E. THE ENERGY SPECS INDICATE A R-33, PLEASE
 PROVIDE HOW MUCH INSULATION IT WILL TAKE TO PROVIDE
 THIS VALUE.
  
 .
  
 8) SEMI- COMPLIED. SHEETA-2.2 & A-4.1. SHEET A-2.2
 DETIAL # 1 SHOWS THE USE OF 1 INCH RIGID INSULATION
 BOARD AND THE 5/8 INCH DRYWALL EXTENDING 6 IN. ABOVE
 THE CEILING LEAVING THE INSULATION BOARD EXPOSED ABOVE
 THE CEILING. PLEASE PROVIDE COMPLIANCE WITH 2603.4
 THERMAL BARRIERS OR 2603.4.1. PROVIDE THE MANUFACTURERS
 SPEC SHEET FOR THE 1 INCH RIGID INSULATION, INCLUDE
 FLAME SPREAD & SMOKE DEVELOPMENT.
  
 9A) DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF
 RECORD.
 MISSING PRODUCT APPROVALS, MAY BE SUBMITTED AS DEFERRED
 SUBMITTALS UPON WRITTEN REQUEST:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STAND
  
 9B)DEFERRED SUBMITTAL, REQUEST BY THE DESIGNER OF
 RECORD.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) NEW COMMENT!!!!! THIS BUILDING QUALIFIES AS A
 THRESHOLD BUILDING, AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 500 OCCUPANTS & 5,000 SQ.
 FT. IN AREA. PLEASE SEE NEW COMMENTS THAT WILL BE
 REQUIRED AS A THRESHOLD BUILDING. THIS MORNING I
 E-MAILED MATTHEW SLATTER THE REQUIREMENTS FOR A
 THRESHOLD BUILDING AND FORMS THAT WILL BE REQUIRED TO
 BE SIGNED.
  
 10A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 10B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. PLEASE FILE OUT
 FORMS BY ALL INTERESTED PARTIES.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 10C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 10D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 10D)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 10E) NOTICE!!!! PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
  
 10F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 10G) NOTE SINCE THIS IS A THRESHOLD PROJECT (3) SETS OF
 PLANS, REPORTS, AND PRODUCT APPROVALS WILL BE REQUIRED,
 A 3RD SET WILL BE FOR THE THRESHOLD INSPECTORS USE.
  
 11A) NOTICE THIS BUILDING CAN NO LONGER BE CLASSIFIED
 AS A BUILDING CATEGORY II WITH A OCCUPANT LOAD OF 762
 OCCUPANTS. ASCE 7-10 TABLE 1.5-1 RISK AS WELL AS 2010
 FBC-B TABLE 1604.5. BUILDINGS FOR PUBLIC ASSEMBLY WITH
 OCCUPANT LOADS GREATER THAN 300.
 CATEGORIES LIST THIS AS A CATEGORY III WHICH WILL
 INCREASE THE PRESSURES SINCE THE WIND SPEED VULT WILL
 BE 180 MPH.
  
 THIS WILL EFFECT SHEET S-6 WITH ALL PRESSUES FLAT ROOF,
 SLPOED ROOFS (5:12 PITCH) AS WELL AS WALL PRESSURES IN
 ZONES 4 & 5. PLEASE UPDATE CHARTS. INDICATE IF
 PRESSURES ARE VULT OR VASD. THERE ARE ALSO PRESSURES
 THAT ARE TAKEN FROM RAS 128 FOR BUILDINGS THAT ARE LESS
 THAN 40 FT IN HEIGHT, EXPOSURE "C" FOR A FLAT ROOF,
 PLEASE NOTE THESE PRESSURES CAN ONLY BE USED FOR
 BUILDING CATEGORY II BUILDINGS.
  
 11B) SHEET S-6 ALSO IS MISSING THE WALL PRESSURES FOR
 WALL ZONES 4 & 5. COMPONENTS & CLADDING PRESSURES
 POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 12-13) COMPLIED.
  
 14) NEW COMMENT: THE COMBINED OCCUPANT LOAD OF
 BUILDING, POOL AND POOL DECK IS 1,247 SHOW COMPLIANCE
 WITH:
 2010 FBC-B F] 907.2.1.1 SYSTEM INITIATION IN GROUP A
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 1,000 OR MORE.
 ACTIVATION OF THE FIRE ALARM IN GROUP A OCCUPANCIES
 WITH AN OCCUPANT LOAD OF 1,000 OR MORE SHALL INITIATE A
 SIGNAL USING AN EMERGENCY VOICE/ALARM COMMUNICATIONS
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 EXCEPTION: WHERE APPROVED, THE PRERECORDED ANNOUNCEMENT
 IS ALLOWED TO BE MANUALLY DEACTIVATED FOR A PERIOD OF
 TIME, NOT TO EXCEED 3 MINUTES, FOR THE SOLE PURPOSE OF
 ALLOWING A LIVE VOICE ANNOUNCEMENT FROM AN APPROVED,
 CONSTANTLY ATTENDED LOCATION.
  
 15) ENERGY GAUGE FORM 506-2010 ONLY ONE REPORT WAS
 SUBMITTED, NOTE THAT THE ENGINEEER SEALED THE REPORT
 BUT DID NOT SIGN NOR DATE THE REPORT. 61G15-23.002(2)
 FL. ADMIN. CODE.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  