Plan Review Notes
Plan Review Notes For Permit 14071105
Permit Number 14071105
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-02 12:29:21WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHT. A-0.0- CODE SUMMARY BLOCK - REFERENCE IS MADE
 TO THE 2010 FLORIDA BUILDING CODE W/ BOCA RATON
 AMENDMENTS. REVISE THIS TO READ CITY OF WEST PALM
 BEACK.
 2) THE ADDRESS OF THE PROJECT ON THE APPLICATION DOES
 NOT MATCH THE ADDRESS ON THE PLANS. CORRECT THE PLANS
 TO REFLECT THE CORRECT ADDRESS.
 3) SHT. A-0.0- BUILDING CODE BLOCK- THIS PROJECT IS
 NOTED AS AN A-2 OCCUPANCY. IT IS ACTUALLY A MIXED
 OCCUPANCY OF SEVERAL CLASSIFICATIONS SUCH AS A-1, A-3,
 A-4, B,ETC. HOW CAN THIS BUILDING BE CLASSIFIED AS AN
 A-2 IN IT'S ENTIRETY? CLARIFY.2010FBC SEC.508.1
 4) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES SHALL BE
 BASED ON THE DIFFERENT OCCUPANCIES. 2010 FPC SEC.403.1.
 I AM QUESTIONING YOUR AREA PER PERSON CALCULATIONS ON
 SHT. A-0.0- UNTIL YOU REVISE THE OCCUPANCIES & OCCUPANT
 LOAD, THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
 CANNOT BE DETERMINED
 A) CONCESSION AREA - WHERE ARE YOU GETTING THE 200 SQ.
 FT. PER PERSON FROM?
 B) BOWLING AREA- SHOULD BE 7 SQ. FT. PER PERSONPER FBC
 TABLE 1004.1
 C) THEATRE LOBBY- SHOULD BE 5 SQ. FT. PER PERSON NET
 FOR STANDING AREA.
 5) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2010 FGC SEC.301.3.
 6) SUBMIT A GAS RISER FOR REVIEW. SHOW TYPE OF PIPING
 MATERIAL, LENGTHS OF EACH PIPE SECTION, BTU
 LOAD,COMBUSTION AIR, VENTING, LOCATION OF VALVES,
 METER, REGULATOR, ETC.2010 FGC SECS.304,402.1,.
 7) SHOW THE REQUIRED DIMENSIONS OF THE CLEAR FLOOR
 SPACES FOR THE HANDICAPPED URINAL AND FOR THE FIXTURES
 IN THE ACCESSIBLE TOILET ROOMS.2010 FAC SEC., 305.
 8) SHT. A-1.2- A MINIMUM 30" X 60 " CLEARANCE SHALL BE
 PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER
 COMPARTMENT PER THE 2010 FAC SEC.608.2.2.1.
 9) SHT.A-1.2- SHOW THE LOCATION OF THE GRAB BARS IN THE
 ACCESSIBLE SHOWERS.COMPLY W/ FAC SEC. 608.3.3.
 10) THE LOCATION OF THE SHOWER SPRAY UNIT (HEIGHT)
 SHALL COMPLY WITH THE 2010 FAC SEC.608.5.3. THE MAX.
 HEIGHT IS 48 INCHES ABOVE THE SHOWER FLOOR.
 11) SHT. A-1.2 - THERE IS A NOTE ON THE PLAN THAT
 REFERS TO INTERIOR DESIGN DRAWINGS FOR LOCATIONS AND
 MOUNTING HEIGHTS OF ITEMS IN THE RESTROOMS. THERE ARE
 NO INTERIOR DESIGN DRAWINGS IN THE PLANS. SUBMIT THESE
 DRAWINGS FOR REVIEW.
 12) SHT. A-1.2- THE REAR WALL AND SIDE WALL GRAB BARS
 SHALL COMPLY W/ THE 2010 FAC SECS. 604.5.1 & 604.5.2.
 13)SHT. A-1.2- THE MOUNTING HEIGHT OF THE TOILET PAPER
 DISPENSER SHALL COMPLY W/ THE 2010 FAC SEC.604.7.
 14) SHT. A-1.2.- THE DOOR FOR THE AMBULATORY
 COMPARTMENT STALL SHALL NOT SWING INTO THE STALL PERR
 THE 2010 FAC SEC.604.8.2.2.
 15) SHT.A-4.1- SUBMIT A STORM WATER RISER FOR REVIEW.
 THE SQUARE FOOTAGE OF THE AREAS OF THE SLOPED ROOFS
 THAT DRAIN ONTO THE FLAT ROOF SHALL BE INCLUDED IN THE
 TOAT SQUARE FOOTAGE FOR THE SIZING OF THE STORM SYSTEM.
 WPB ADMIN. AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 16) SHT. A-4.1- VERTICAL LEADER CALCULATIONS- WHERE
 DOES THE 114 SQ. FT. COME FROM?
 17) SHT. A-4.1 - SCUPPERS SHALL BE SIZED PER THE 2010
 FPC SEC.1106.7 & TABLE 1106.7. SUBMIT CALCULATIONS AS
 TO HOW YOU ARRIVED AT THE STATED SIZES.
 18) SHT. A-4.1-FLAT ROOF NOTES- NOTE #8- SCUPPERS SHALL
 NOT HAVE AN OPENING LESS THAN 4 INCHES PER THE 2010 FPC
 SEC.1107.3.
 19) SIZE ALL SECTIONS OF THE SANITARY RISER- ( WET
 SECTIONS OF URINALS, LAVS, HORIZONTAL BRANCH FOR THE
 DRINKING FOUNTAINS, SIZE ALL SECTIONS OF THE FIXTURE
 BRANCHES).
 20) THE DEVELOPED LENGTH FOR THE 2" VENT FROM THE MEN'S
 RESTROOM WATER CLOSETS TO WHERE IT CONNECTS TO THE 3"
 VTR APPEARS THAT IT MAY EXCEED 40 FT. IN LENGTH. IF SO,
 THE 2" VENT SHALL BE INCREASED TO 3" FOR IT'S ENTIRE
 LENGTH PER THE 2010 FPC SEC.916.2. SHOW THE DEVELOPED
 LENGTH ON THE SANITARY RISER.
 21) SHOCK ARRESTORS ARE REQUIRED ON THE REFRIGERATOR
 ICE LINE. 2010 FPC SEC.604.9.
 22) SUBMIT CONSTRUCTION SPECIFICATIONS FOR THE GREASE
 INTERCEPTOR.COMPLY W/2010 FPC SEC.1003.3.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  