2014-09-02 12:29:21 | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. |
| 1) SHT. A-0.0- CODE SUMMARY BLOCK - REFERENCE IS MADE |
| TO THE 2010 FLORIDA BUILDING CODE W/ BOCA RATON |
| AMENDMENTS. REVISE THIS TO READ CITY OF WEST PALM |
| BEACK. |
| 2) THE ADDRESS OF THE PROJECT ON THE APPLICATION DOES |
| NOT MATCH THE ADDRESS ON THE PLANS. CORRECT THE PLANS |
| TO REFLECT THE CORRECT ADDRESS. |
| 3) SHT. A-0.0- BUILDING CODE BLOCK- THIS PROJECT IS |
| NOTED AS AN A-2 OCCUPANCY. IT IS ACTUALLY A MIXED |
| OCCUPANCY OF SEVERAL CLASSIFICATIONS SUCH AS A-1, A-3, |
| A-4, B,ETC. HOW CAN THIS BUILDING BE CLASSIFIED AS AN |
| A-2 IN IT'S ENTIRETY? CLARIFY.2010FBC SEC.508.1 |
| 4) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES SHALL BE |
| BASED ON THE DIFFERENT OCCUPANCIES. 2010 FPC SEC.403.1. |
| I AM QUESTIONING YOUR AREA PER PERSON CALCULATIONS ON |
| SHT. A-0.0- UNTIL YOU REVISE THE OCCUPANCIES & OCCUPANT |
| LOAD, THE MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES |
| CANNOT BE DETERMINED |
| A) CONCESSION AREA - WHERE ARE YOU GETTING THE 200 SQ. |
| FT. PER PERSON FROM? |
| B) BOWLING AREA- SHOULD BE 7 SQ. FT. PER PERSONPER FBC |
| TABLE 1004.1 |
| C) THEATRE LOBBY- SHOULD BE 5 SQ. FT. PER PERSON NET |
| FOR STANDING AREA. |
| 5) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS |
| APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER |
| THE 2010 FGC SEC.301.3. |
| 6) SUBMIT A GAS RISER FOR REVIEW. SHOW TYPE OF PIPING |
| MATERIAL, LENGTHS OF EACH PIPE SECTION, BTU |
| LOAD,COMBUSTION AIR, VENTING, LOCATION OF VALVES, |
| METER, REGULATOR, ETC.2010 FGC SECS.304,402.1,. |
| 7) SHOW THE REQUIRED DIMENSIONS OF THE CLEAR FLOOR |
| SPACES FOR THE HANDICAPPED URINAL AND FOR THE FIXTURES |
| IN THE ACCESSIBLE TOILET ROOMS.2010 FAC SEC., 305. |
| 8) SHT. A-1.2- A MINIMUM 30" X 60 " CLEARANCE SHALL BE |
| PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER |
| COMPARTMENT PER THE 2010 FAC SEC.608.2.2.1. |
| 9) SHT.A-1.2- SHOW THE LOCATION OF THE GRAB BARS IN THE |
| ACCESSIBLE SHOWERS.COMPLY W/ FAC SEC. 608.3.3. |
| 10) THE LOCATION OF THE SHOWER SPRAY UNIT (HEIGHT) |
| SHALL COMPLY WITH THE 2010 FAC SEC.608.5.3. THE MAX. |
| HEIGHT IS 48 INCHES ABOVE THE SHOWER FLOOR. |
| 11) SHT. A-1.2 - THERE IS A NOTE ON THE PLAN THAT |
| REFERS TO INTERIOR DESIGN DRAWINGS FOR LOCATIONS AND |
| MOUNTING HEIGHTS OF ITEMS IN THE RESTROOMS. THERE ARE |
| NO INTERIOR DESIGN DRAWINGS IN THE PLANS. SUBMIT THESE |
| DRAWINGS FOR REVIEW. |
| 12) SHT. A-1.2- THE REAR WALL AND SIDE WALL GRAB BARS |
| SHALL COMPLY W/ THE 2010 FAC SECS. 604.5.1 & 604.5.2. |
| 13)SHT. A-1.2- THE MOUNTING HEIGHT OF THE TOILET PAPER |
| DISPENSER SHALL COMPLY W/ THE 2010 FAC SEC.604.7. |
| 14) SHT. A-1.2.- THE DOOR FOR THE AMBULATORY |
| COMPARTMENT STALL SHALL NOT SWING INTO THE STALL PERR |
| THE 2010 FAC SEC.604.8.2.2. |
| 15) SHT.A-4.1- SUBMIT A STORM WATER RISER FOR REVIEW. |
| THE SQUARE FOOTAGE OF THE AREAS OF THE SLOPED ROOFS |
| THAT DRAIN ONTO THE FLAT ROOF SHALL BE INCLUDED IN THE |
| TOAT SQUARE FOOTAGE FOR THE SIZING OF THE STORM SYSTEM. |
| WPB ADMIN. AMEND. TO 2010 FBC SEC.107.3.5.1.3. |
| 16) SHT. A-4.1- VERTICAL LEADER CALCULATIONS- WHERE |
| DOES THE 114 SQ. FT. COME FROM? |
| 17) SHT. A-4.1 - SCUPPERS SHALL BE SIZED PER THE 2010 |
| FPC SEC.1106.7 & TABLE 1106.7. SUBMIT CALCULATIONS AS |
| TO HOW YOU ARRIVED AT THE STATED SIZES. |
| 18) SHT. A-4.1-FLAT ROOF NOTES- NOTE #8- SCUPPERS SHALL |
| NOT HAVE AN OPENING LESS THAN 4 INCHES PER THE 2010 FPC |
| SEC.1107.3. |
| 19) SIZE ALL SECTIONS OF THE SANITARY RISER- ( WET |
| SECTIONS OF URINALS, LAVS, HORIZONTAL BRANCH FOR THE |
| DRINKING FOUNTAINS, SIZE ALL SECTIONS OF THE FIXTURE |
| BRANCHES). |
| 20) THE DEVELOPED LENGTH FOR THE 2" VENT FROM THE MEN'S |
| RESTROOM WATER CLOSETS TO WHERE IT CONNECTS TO THE 3" |
| VTR APPEARS THAT IT MAY EXCEED 40 FT. IN LENGTH. IF SO, |
| THE 2" VENT SHALL BE INCREASED TO 3" FOR IT'S ENTIRE |
| LENGTH PER THE 2010 FPC SEC.916.2. SHOW THE DEVELOPED |
| LENGTH ON THE SANITARY RISER. |
| 21) SHOCK ARRESTORS ARE REQUIRED ON THE REFRIGERATOR |
| ICE LINE. 2010 FPC SEC.604.9. |
| 22) SUBMIT CONSTRUCTION SPECIFICATIONS FOR THE GREASE |
| INTERCEPTOR.COMPLY W/2010 FPC SEC.1003.3.4. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE- |
| CHIEF PLUMBING INSPECTOR |
| TEL:561-805-6692 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |