Plan Review Notes
Plan Review Notes For Permit 14071105
Permit Number 14071105
Review Stop M
Sequence Number 1
Notes
Date Text
2014-08-18 11:29:538/18/14
 NOTES:
 1.PAGE 9OF 9 OF THE ENERGY CALCULATIONS MUST BE
 COMPLETELY FILLED OUT.
 2.INDICATE ON THE A/C SCHEDULE THE EER/SEER OF THE A/C
 EQUIPMENT AS REQUIRED BY THE ENERGY CALCULATIONS.
 3.PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 THE FIRE PLACE.
 4..SHOW ON PLANS COMPETE DETAIL OF THE CONDENSING UNIT
 INSTALLATION ON THE ROOF AND INDICATE HOW THE STAND IS
 SECURED TO ROOF AND THE UNIT TO THE STAND.
 5.PROVIDE COMPLETE KITCHEN EXHAUST HOOD INSTALLATION
 DATAILS(TYPE 1) AS REQUIRED BY FMC SEC.506 AND 507.
 6.PROVIDE COMPLETE FIRE SUPPRESSION PLANS AS REQUIRED
 BY THE FMC SEC.509.
 7.SHOW ON PLANS THE DISCHARGE LOCATION OF THR
 CONDENSATE AS REQUIRED BY SEC.307 OF THE FMC AND
 SEC.1503.7 OF THE FBC.
  
 REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT
 561-805-6732.