2014-08-01 09:18:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| SHEET LS-1 SHOWS A THEATER LOBBY WITH EXIT PATH PASSING |
| THROUGH IT. THE THEATER LOBBY SHALL COMPLY WITH THE |
| REQUIRNEMENTS OF NFPA 101, CHAPTER 12, NEW ASSEMBLY |
| OCCUPANCIES, 12.1.7.2 WAITING SPACES. STANDING OR |
| WAITING IN THE AREA OF THE EXIT PATHWAY BY REQUIRMENT |
| SHALL BE RESTRICTED. THE MEANS OF RESTRICTION SHALL BE |
| REVIEWED AND APPROVED THROUGH THE OFFICE OF THE FIRE |
| MARSHAL. |
| |
| NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| DOOR. |
| |
| ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH |
| NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. |
| |
| |
| |
| A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING |
| FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN |
| EMERGENCY AT ANY TIME. |
| |