Plan Review Notes
Plan Review Notes For Permit 14071105
Permit Number 14071105
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-08-01 09:18:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 SHEET LS-1 SHOWS A THEATER LOBBY WITH EXIT PATH PASSING
 THROUGH IT. THE THEATER LOBBY SHALL COMPLY WITH THE
 REQUIRNEMENTS OF NFPA 101, CHAPTER 12, NEW ASSEMBLY
 OCCUPANCIES, 12.1.7.2 WAITING SPACES. STANDING OR
 WAITING IN THE AREA OF THE EXIT PATHWAY BY REQUIRMENT
 SHALL BE RESTRICTED. THE MEANS OF RESTRICTION SHALL BE
 REVIEWED AND APPROVED THROUGH THE OFFICE OF THE FIRE
 MARSHAL.
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
  
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME.
  