Plan Review Notes
Plan Review Notes For Permit 14071105
Permit Number 14071105
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-14 13:51:18 
 14071105
 1517 CAMERON SAMUEL LANE
 CLUBHOUSE BUILDING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. PROVIDE A FIXTURE SCHEDULE FOR THE
 LIGHTING SYSTEM. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PANEL P1 AND P2 MAY NOT BE LOCATED IN A STORAGE ROOM.
 PANEL BOARDS SHALL BE LOCATED IN DEDICATED SPACES. NEC
 240.24(D), 110.26 (A) THRU (G).
  
 RECEPTACLES LOCATED OUTSIDE ADJACENT TO THE LOGGIA
 REQUIRE GFCI PROTECTION. NEC 210.8
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6700
  
  
  