2014-08-26 16:45:03 | BUILDING PLAN REVIEW |
| PERMIT:14071105 |
| ADD: 1517 CAMERON SAMUEL LN. |
| CONT: KAST |
| TEL: (561)346-4994 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 26/2014 |
| ACTION: DENIED |
| |
| 1A) THE PLANS NEED TO HAVE THE CORRECT ADDRESS OF 1517 |
| CAMERON SAMUEL LN. ON ALL PLANS. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 1B) THE STRUCTURAL PLANS HAVE STICKERS ON PLANS AND |
| HAND WRITTEN NOTES. NO SSTICKEERS ARE TO BE PLACED ON |
| THE PLANS. 107.2.1.4 QUALITY OF BUILDING PLANS. |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. |
| |
| 2) THE PLAN INDEX INDICATES THERE IS A SITE PLAN A-0.1, |
| MISSING FROM THE SET OF PLANS, PLEASE INCLUDE THE SITE |
| PLAN: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 1. SITE REQUIREMENTS: |
| PARKING |
| FIRE ACCESS |
| VEHICLE LOADING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| |
| 3) STRUCTURAL SHEET S-6 INDICATES A SOILS REPORT WAS |
| COMPLETED BY D & N DRILLING ENGINEERING 1/20/2014. |
| PLEASE SUBMIT 2 ORIGINAL SIGNED & SEALED REPORTS. |
| 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 4) COVERSHEET: THE BUILDING CODE ANALYSIS INDICATES |
| THIS BUILDING TO BE A FIRE SPRINKLERED BUILDING. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS.:107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.5 |
| . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| FIRE SPRINKLERS |
| |
| 5) THE COVERSHEET INDICATES THE OCCUPANCY IN THE |
| FITNESS CENTER NEITHER SHEET A-1.0 NOR A-1.1 SHOW |
| EQUIPMENT LAYOUT IN THE GYM, THEN |
| 15 SQ FT / OCCUPANT WILL BE TAKEN FOR THE SPACE. 2010 |
| FBC-B 1004.1.1. |
| |
| 6) SHEET A-1.0: |
| 6A) SHEET A-1.0 VERSES THE STRUCTURAL SHEET S3, THE |
| FIRE BOX IN THE ARCHITECTURAL SHEET SHOWS A 3X8 AND THE |
| STRUCTURAL SHEET SHOWS A 3X6 FOOT FIRE BOX. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED, DISCREPANCY IN |
| PLANS. |
| |
| 6B) THE THEATER SEATING SHOW RAISED SEATING, THE S6 |
| SHEET SHOWS GEO FOAM NO MANUFACTURERS SPECS WERE |
| SUBMITTED NOR DOES THE PLANS INDICATE THE END OF THE |
| FOAM ARE ENCAPSULATED BY CONCRETE ON THE SIDES. FBC-B |
| 2603.4.1.1. |
| |
| 7) SHEET A4.1 INDICATES THE USE OF ICYNENE INSULATION |
| AS WELL AS THE COVER SHEET ALSO HAS NOTESFOR ICYNENE. |
| PLEASE SUBMIT THE FULL ICYNENE REPORT LISTED ERS 1826 |
| FOR REVIEW; 2010 FBC-B 2603.4.1.6. PLEASE PROVIDE WHICH |
| AREAS ARE GOING TO HAVE ICYNENE TYPE INSULATION AND |
| WHICH AREAS OF THE ROOFING ARE GOING TO HAVE ROOF TOP |
| INSULATION ON TOP OF THE ROOF DECK AS DEPICTED IN |
| DETAILS B-E. THE ENERGY SPECS INDICATE A R-33, PLEASE |
| PROVIDE HOW MUCH INSULATION IT WILL TAKE TO PROVIDE |
| THIS VALUE. |
| |
| 8) SHEET A4.1 ALSO SHOWS EXTERIOR WALL CONSTRUCTION IN |
| DETAILS C& D, NO INSULATION IS DEPICTED IN THESE |
| DETAILS, THE ENERGY CALCULATIONS INDICATE A R VALUE OF |
| 8.0. ENERGY 502..2 PERSCRIPTIVE. |
| |
| 9) MISSING PRODUCT APPROVALS, MAY BE SUBMITTED AS |
| DEFERRED SUBMITTALS UPON WRITTEN REQUEST: |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STAND |
| |
| 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 11A) SHEET S-6 DOES HAVE ROOF PRESSURES ZONE #1 @ 24.6, |
| ZONE @ 38.8 & ZONE 3 @ 67.1 THESE PRESSUES DO NOT |
| INDICATE IF VULT, VASD, WHAT THE MEAN ROOF HEIGHT? |
| THERE ARE ALSO PRESSURES THAT ARE TAKEN FROM RAS 128 |
| FOR BUILDINGS THAT ARE LESS THAN 40 FT IN HEIGHT, |
| EXPOSURE "C" FOR A FLAT ROOF, VASD FOR 20 SQ FTPLEASE |
| PROVIDE THE VALUES FOR 10 SQ FTTHEY ARE TAKEN FOR THE |
| FASTENERS OF THE ROOFING PRODUCT WORSE CASE AT 10 SQ. |
| FT. |
| |
| 11B) SHEET S-6 DOES NOT PROVIDE WHAT THE PRESSURES ARE |
| FOR 5:12 PITCH ROOF? COMPONENTS & CLADDING PRESSURES |
| POSITVE & NEGATIVE TABLE 1609.2(2) . |
| |
| 11C) SHEET S-6 ALSO IS MISSING THE WALL PRESSURES FOR |
| WALL ZONES 4 & 5. COMPONENTS & CLADDING PRESSURES |
| POSITVE & NEGATIVE TABLE 1609.2(2) . |
| |
| 12) SHEET S-6 NOTES FOR BUCK ATTACHMENT REFERANCE THE |
| FBC-R 4409.10.1 RESIDENTIAL CODE, THIS IS CONSIDERED A |
| COMMERCIAL BUILDING. |
| |
| 13) SHEET S-6 WIRE LATH @ WIRE FASTENERS PLEASE PROVIDE |
| WHERE WIRE STAPLES CAN BE USED FOR FASTENING WIRE LATH |
| WITH A 1 1/2 EMBEDMEMT. 2510.3 INSTALLATION. |
| INSTALLATION OF THESE MATERIALS SHALL BE IN COMPLIANCE |
| WITH ASTM C 926 AND ASTM C 1063. 3/8 INCH RIB LATH IS |
| TO BE NAILED AT EVERY RIB. |
| ASTM C 1063 7.10.2.3 EXPANDED 3/8 IN REIB LATH AND |
| SHEET EXPANDED METAL LATH SHALL BE ATTACHED TO |
| HORIZONTAL AND VERTICAL WOOD FRAMING MEMBRS WITH NAILS |
| OR STAPLES TO PROVIDE AT LEAST 1 3/4 INCH PENETRTION |
| INTO HORIZONTAL WOOD FRAMING MEMBERS AND 3/4 INCH |
| PENETRATION INTO VERTICAL FRAMING MEMBERS. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |