Plan Review Notes For Permit 14071055 |
Permit Number |
14071055 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-29 13:25:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SHEET A2, LIFE SAFETY PLAN: | | PROVIDE DIMENSIONS IN EXPANDED DINING TO INCLUDE AISLE | | WIDTH FOR SEATING AT TABLES THAT MEET THE REQUIRMENTS | | OF NFPA 101 CHAPTER 7. | | | | IF THE DRAWING SHOWN IS A FENCE OR RAILING, PROVIDE FOR | | AN EXIT FROM THE EXTERIOR DINING AREA THAT DOES NOT | | LEAD BACK INTO THE BUILDING. | | | | PROVIDE A SITE PLAN THAT SHOWS IF AN EXIT IS PROVIDED | | TO EXTERIOR DINING THE EXIT DISCHARGE LEADS TO A PUBLIC | | WAY. | | | | THE DOOR LEADING FROM THE WAITRESS STATION TO THE REAR | | EXPANDED DINING AREA SHALL OPEN AND IMPEDE THE EXIT | | PATH AS SHOWN. THE DOOR SHALL SWING INTO THE WAITRESS | | STATION. | | | | THE DIMENSIONS OF THE CORRIDOR BETWEEN THE EXPANDED | | DINING AREAS SHALL HAVE A DIMENSION PROVIDED THAT MEETS | | THE MINIMUM REQUIRMENTS OF NFPA 101, CHAPTER 7. | | | | PROVIDE DIMENSIONS OF EACH EXPANDED DINING AREA AND | | CONFIRM THAT THE OCCUPANCY LOAD AND SEATING MEETS THE | | REQUIREMENTS NFP 101, CHAPTER 7. |
|