Plan Review Notes For Permit 14071032 |
Permit Number |
14071032 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-30 16:56:09 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) CUT SHEETS WERE SUBMITTED FOR A HEAT PUMP AND HEAT | | PUMP TIE DOWN. THERE IS NO WIRING DIAGRAM FOR THE HEAT | | PUMP SHOWN ON THE ELECTRICAL DIAGRAM ON PAGE 3 OF THE | | PLANS AND PAGE 1 HAS N/A SPECIFIED FOR HEATER. PLEASE | | CORRECT. CITY AMENDMENTS 107.2.1 | | | | 2) SPECIFY WHICH ONE OF THE HEAT PUMP MODELS WILL BE | | INSTALLED AND PROVIDE LOAD CALCULATIONS TO SHOW | | ADEQUATE ELECTRIC SERVICE. CITY AMENDMENTS 107.2.1 AND | | NEC 220.40 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|