2014-07-30 16:56:092010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) CUT SHEETS WERE SUBMITTED FOR A HEAT PUMP AND HEAT
 PUMP TIE DOWN. THERE IS NO WIRING DIAGRAM FOR THE HEAT
 PUMP SHOWN ON THE ELECTRICAL DIAGRAM ON PAGE 3 OF THE
 PLANS AND PAGE 1 HAS N/A SPECIFIED FOR HEATER. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 2) SPECIFY WHICH ONE OF THE HEAT PUMP MODELS WILL BE
 INSTALLED AND PROVIDE LOAD CALCULATIONS TO SHOW
 ADEQUATE ELECTRIC SERVICE. CITY AMENDMENTS 107.2.1 AND
 NEC 220.40
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]