Plan Review Notes For Permit 14070978 |
Permit Number |
14070978 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-09-18 12:08:48 | 1) THE CALCULATIONS YOU HAVE PROVIDED FOR THE SIZING OF | | THE GREASE INTERCEPTOR ARE INADEQUATE. THE GALLONS OF | | WASTE PER SEAT THAT YOU HAVE USED (10 GALS.) IS | | INADEQUATE. YOU WILL NEED TO USE A FACTOR OF 25 GALS. | | OER SEAT. THIS WILL REQUIRE 2-1200 GALLON TANKS IN | | SERIES TO COMPLY. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|