2014-08-27 08:32:54PLUMBING PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND EVIEW
 DATE: WED. AUG. 27/ 2014
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
 1)2ND REQUEST. SHEET 7 GREASY WASTE ISOMETRIC. SHOW THE
 COMPLETE GREASY WASTE NO BREAK LINES, ALSO SHOW WHAT IS
 BEING ELIMINATED FROM THE GREASY WASTE SYSTEM.IS THE
 COMPLETE GREASY WASTE INTERCEPTOR ABOVE GROUND, BELOW
 GROUND, PROVIDE SIZING OF THE EXISTING GREASE
 INTERCEPTOR, FLOW CONTROL DEVICE AND VENTING 2010 FBC-P
 1003.3.4.1 & 1003.3.4.2.
 MISSING IN THE WASH UP ROOM (3) COMPARTMENT
 SINK,SERVICE SINK, HAND SINK AND DISHWASHER AND THE (1)
 REMAINING TRENCH DRAIN UNDER THE 3 COMPARMENT SINK.
 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR
 OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 2) 2ND REQUEST MISSING REQUIRED FIXTURES. SHEET 7
 PLEASE PROVIDE THE FORMULA USED FOR SIZING OF THE
 EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR SHALL
 BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE SECTION
 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW CONTROL
 (1003.3.4.2) OR FOR CONCRETE VAULT TYPE INTERCEPTORS
 (TABLE 1003.5.1).
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3
 COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE
 SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8.
  
 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED
 FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP.
  
 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE
 FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH
 AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE
 RECEPTOR IN ACCORDANCE WITH SECTION 802.2.
  
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 4) PROVISO: BE VARIFIED IN FIELD!!!! SHEET 7 SHOWS (3)
 COMPARTMENT SINKS, HAND SINKS, DISHWASHER WASTE(NOT
 SHOWN) WITH NO TRAPS. PLEASE REVIEW 2010 FBC-P 802.2
 INSTALLATION. ALL INDIRECT WASTE PIPING SHALL DISCHARGE
 THROUGH AN AIR GAP OR AIR BREAK INTO A WASTE RECEPTOR
 OR STANDPIPE. WASTE RECEPTORS AND STANDPIPES SHALL BE
 TRAPPED AND VENTED AND SHALL CONNECT TO THE BUILDING
 DRAINAGE SYSTEM. ALL INDIRECT WASTE PIPING THAT EXCEEDS
 2 FEET (610 MM) IN DEVELOPED LENGTH MEASURED
 HORIZONTALLY, OR 4 FEET (1219 MM) IN TOTAL DEVELOPED
 LENGTH, SHALL BE TRAPPED.
  
 5) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR
 POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES
 REQUIRING POTABLE WATER. ICE MACHINES, ICE CHEST WHICH
 REQUIRE INDIRECT WASTE AND COMPLIANCE TO WITH 802.1.3
 POTABLE CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO
 THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 6) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR
 POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES
 REQUIRING POTABLE WATER:
 SEE THE 2010 FBC-P:
 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED
 WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM.
 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE
 DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  