2014-08-27 08:32:54 | PLUMBING PLAN REVIEW |
| PERMIT: 14070978 |
| ADD: 330 CLEMATIS ST #107 |
| CONT: SCALTEC USA CORP |
| TEL: (561)922-1888 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND EVIEW |
| DATE: WED. AUG. 27/ 2014 |
| ACTION: DENIED |
| |
| NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| CODE VIOLATION. |
| |
| 1)2ND REQUEST. SHEET 7 GREASY WASTE ISOMETRIC. SHOW THE |
| COMPLETE GREASY WASTE NO BREAK LINES, ALSO SHOW WHAT IS |
| BEING ELIMINATED FROM THE GREASY WASTE SYSTEM.IS THE |
| COMPLETE GREASY WASTE INTERCEPTOR ABOVE GROUND, BELOW |
| GROUND, PROVIDE SIZING OF THE EXISTING GREASE |
| INTERCEPTOR, FLOW CONTROL DEVICE AND VENTING 2010 FBC-P |
| 1003.3.4.1 & 1003.3.4.2. |
| MISSING IN THE WASH UP ROOM (3) COMPARTMENT |
| SINK,SERVICE SINK, HAND SINK AND DISHWASHER AND THE (1) |
| REMAINING TRENCH DRAIN UNDER THE 3 COMPARMENT SINK. |
| 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC |
| GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR |
| OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO |
| RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH |
| GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, |
| SUCH AS IN RESTAURANTS. FIXTURES AND EQUIPMENT SHALL |
| INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR |
| SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS |
| INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT |
| ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. |
| |
| 2) 2ND REQUEST MISSING REQUIRED FIXTURES. SHEET 7 |
| PLEASE PROVIDE THE FORMULA USED FOR SIZING OF THE |
| EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR SHALL |
| BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE SECTION |
| 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW CONTROL |
| (1003.3.4.2) OR FOR CONCRETE VAULT TYPE INTERCEPTORS |
| (TABLE 1003.5.1). |
| |
| THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| FAHRENHEIT (65.56 DEGREES CELSIUS). |
| |
| 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3 |
| COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE |
| SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED. |
| FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL |
| DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED |
| IN SECTIONS 802.1.1 THROUGH 802.1.8. |
| |
| 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED |
| FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL |
| DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN |
| AIR GAP. |
| |
| 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE |
| FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH |
| AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE |
| RECEPTOR IN ACCORDANCE WITH SECTION 802.2. |
| |
| 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF |
| UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE |
| PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE |
| INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR |
| DIRECTLY CONNECT TO THE DRAINAGE SYSTEM. |
| |
| 4) PROVISO: BE VARIFIED IN FIELD!!!! SHEET 7 SHOWS (3) |
| COMPARTMENT SINKS, HAND SINKS, DISHWASHER WASTE(NOT |
| SHOWN) WITH NO TRAPS. PLEASE REVIEW 2010 FBC-P 802.2 |
| INSTALLATION. ALL INDIRECT WASTE PIPING SHALL DISCHARGE |
| THROUGH AN AIR GAP OR AIR BREAK INTO A WASTE RECEPTOR |
| OR STANDPIPE. WASTE RECEPTORS AND STANDPIPES SHALL BE |
| TRAPPED AND VENTED AND SHALL CONNECT TO THE BUILDING |
| DRAINAGE SYSTEM. ALL INDIRECT WASTE PIPING THAT EXCEEDS |
| 2 FEET (610 MM) IN DEVELOPED LENGTH MEASURED |
| HORIZONTALLY, OR 4 FEET (1219 MM) IN TOTAL DEVELOPED |
| LENGTH, SHALL BE TRAPPED. |
| |
| 5) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR |
| POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES |
| REQUIRING POTABLE WATER. ICE MACHINES, ICE CHEST WHICH |
| REQUIRE INDIRECT WASTE AND COMPLIANCE TO WITH 802.1.3 |
| POTABLE CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO |
| THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE |
| THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| |
| 6) 2ND REQUEST. THE PLANS DO NOT PROVIDE ANY PLANS FOR |
| POTABLE WATER OR THE HOOK UP OF ANY APPLIANCES |
| REQUIRING POTABLE WATER: |
| SEE THE 2010 FBC-P: |
| 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS. |
| ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS |
| INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT |
| CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED |
| WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF |
| THE WATER SUPPLY SYSTEM. |
| 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE |
| DISPENSERS. |
| THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND |
| NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED |
| AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO |
| ASSE 1022 OR BY AN AIR GAP. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |