2014-09-03 14:20:26DATE: 9/3/2014
 PROJECT: SUSHI YAMA
 PERMIT#: 14070978
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS.
  
 1) PROVIDE POWER RISER DIAGRAM INDICATING THE LOCATION
 OF THE ELECTRICAL SERVICE ON THE BUILDING AND THE SIZE
 OF THE DISCONNECTS AND FEEDERS.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE
 BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE
 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 5) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR
 AIR CONDITIONING AND REFRIGERATION EQUIPMENT.
  
 6) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. SEE NEC 210.63,
 210.8(A)(3), AND 406.8(B)(1),
  
 7) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN
 HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE
 SEQUESNCE OF EVENTS UPON ACTIVATION.
  
 8) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD
 FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM,
 NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  