2014-09-03 14:20:26 | DATE: 9/3/2014 |
| PROJECT: SUSHI YAMA |
| PERMIT#: 14070978 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| DUPLICATE COMMENTS. |
| |
| 1) PROVIDE POWER RISER DIAGRAM INDICATING THE LOCATION |
| OF THE ELECTRICAL SERVICE ON THE BUILDING AND THE SIZE |
| OF THE DISCONNECTS AND FEEDERS. |
| |
| 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 4) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE |
| BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE |
| 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| |
| 5) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR |
| AIR CONDITIONING AND REFRIGERATION EQUIPMENT. |
| |
| 6) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL |
| EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME |
| LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, |
| AND REFRIGERATION EQUIPMENT. SEE NEC 210.63, |
| 210.8(A)(3), AND 406.8(B)(1), |
| |
| 7) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN |
| HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE |
| SEQUESNCE OF EVENTS UPON ACTIVATION. |
| |
| 8) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD |
| FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM, |
| NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |