Plan Review Notes
Plan Review Notes For Permit 14070978
Permit Number 14070978
Review Stop P
Sequence Number 1
Notes
Date Text
2014-08-04 08:31:29PLUMBING PLAN REVIEW
 PERMIT: 14070978
 ADD: 330 CLEMATIS ST #107
 CONT: SCALTEC USA CORP
 TEL: (561)922-1888
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1STREVIEW
 DATE: MON. AUG. 04/ 2014
 ACTION: DENIED
  
 1) SHEET 7 SHOWS THE GREASY WASTE ISOMETRIC, PLEASE
 SHOW THE COMPLETE GREASY WASTE TO THE GREASE
 INTERCEPTOR, MISSING THE WASH UP ROOM WITH (3)
 COMPARTMENT SINK,SERVICE SINK, HAND SINK AND
 DISHWASHER. 2010 FBC-P 003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. A GREASE
 INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE
 REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES AND
 EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS. FIXTURES AND
 EQUIPMENT SHALL INCLUDE POT SINKS, PRERINSE SINKS; SOUP
 KETTLES OR SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS
 OR SINKS INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD
 WASH UNITS AND DISHWASHERS WITHOUT PRERINSE
 SINKS.GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED.
  
 2) SHEET 7 PLEASE PROVIDE THE FORMULA USED FOR SIZING
 OF THE EXISTING GREASE INTERCEPTOR. GREASE INTERCEPTOR
 SHALL BE DESIGNED UNDER THE 2010 FBC-PLUMBING CODE
 SECTION 1003.3.4 TOTAL FLOW RATE WITH RATE OF FLOW
 CONTROL (1003.3.4.2) OR FOR CONCRETE VAULT TYPE
 INTERCEPTORS (TABLE 1003.5.1).
  
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 3) THE GREASY WASTE ISOMETRIC SHOWS HAND SINKS, 3
 COMPARTMENT SINKS TIED IN DIRECTLY TO THE GREASY WASTE
 SANITARY. PLEASE REVIEW 2010 FBC-P 02.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8.
  
 802.1.1 FOOD HANDLING. EQUIPMENT AND FIXTURES UTILIZED
 FOR THE STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP.
  
 02.1.7 COMMERCIAL DISHWASHING MACHINES. THE DISCHARGE
 FROM A COMMERCIAL DISHWASHING MACHINE SHALL BE THROUGH
 AN AIR GAP OR AIR BREAK INTO A STANDPIPE OR WASTE
 RECEPTOR IN ACCORDANCE WITH SECTION 802.2.
  
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 4) SHEET 7 SHOWS (3) COMPARTMENT SINKS, HAND SINKS,
 DISHWASHER WASTE(NOT SHOWN) WITH NO TRAPS. PLEASE
 REVIEW 2010 FBC-P 802.2 INSTALLATION. ALL INDIRECT
 WASTE PIPING SHALL DISCHARGE THROUGH AN AIR GAP OR AIR
 BREAK INTO A WASTE RECEPTOR OR STANDPIPE. WASTE
 RECEPTORS AND STANDPIPES SHALL BE TRAPPED AND VENTED
 AND SHALL CONNECT TO THE BUILDING DRAINAGE SYSTEM. ALL
 INDIRECT WASTE PIPING THAT EXCEEDS 2 FEET (610 MM) IN
 DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 4 FEET (1219
 MM) IN TOTAL DEVELOPED LENGTH, SHALL BE TRAPPED.
  
 5) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER
 OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE
 WATER. ICE MACHINES, ICE CHEST WHICH REQUIRE INDIRECT
 WASTE AND COMPLIANCE TO WITH 802.1.3 POTABLE
 CLEAR-WATER WASTE. DISCHARGE POTABLE WATER TO THE
 BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 6) THE PLANS DO NOT PROVIDE ANY PLANS FOR POTABLE WATER
 OR THE HOOK UP OF ANY APPLIANCES REQUIRING POTABLE
 WATER:
 SEE THE 2010 FBC-P:
 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM, SHALL BE PROVIDED
 WITH PROTECTION AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM.
 608.16.10 COFFEE MACHINES AND NONCARBONATED BEVERAGE
 DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  