2014-08-12 14:01:32 | DATE: 8/6/2014 |
| PROJECT: SUSHI YAMA |
| PERMIT#: 14070978 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. FBC 107.2.1 PLEASE PROVIDE |
| ADDITIONAL DETAIL TO THE PLANS AS FOLLOWS: |
| |
| 2) PROVIDE ALLL CIRCUITRY ON THE FLOOR PLAN AND PANEL |
| SCHEDULE, INCLUDE THE EXISTING OUTLETS, AND AS WELL AS |
| THE NEW OUTLETS AND DISCONNECTS AS REQUIRED TO MATCH |
| THE EQUIPMENT PLAN AS INDICATED ON SHEET 5. |
| |
| 3) PROVIDE POWER RISER DIAGRAM, AND THE LOCATION OF THE |
| ELECTRICAL SERVICE ON THE BUILDING. |
| |
| 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 6) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE |
| BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE |
| 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| |
| 7) PROVIDE A LIGHTING PLAN, INDICATE ALL GENERAL |
| PURPOSE LIGHTING TASK LIGHTING, SPECIALTY LIGHTING, |
| SECURITY LIGHTING, EXIT AND EMERGENCY LIGHTING TO |
| COORDINATE WITH THE LIFE SAFETY PLAN. |
| |
| 8) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR |
| AIR CONDITIONING AND REFRIGERATION EQUIPMENT. |
| |
| 9) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL |
| EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME |
| LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, |
| AND REFRIGERATION EQUIPMENT. SEE NEC 210.63, |
| 210.8(A)(3), AND 406.8(B)(1), |
| |
| 10) PROVIDE LIGHTING CONTROL. FBC-ENERGY |
| A. 505.2 LIGHTING CONTROLS (MANDATORY). |
| LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| 505.2.4. |
| AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS |
| LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED |
| WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING |
| IN THOSE AREAS. |
| |
| B. 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| ASTRONOMICAL TIME SWITCH. |
| |
| 11) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN |
| HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE |
| SEQUESNCE OF EVENTS UPON ACTIVATION. WHAT IT CONTROLS |
| AND HOW IT CONTROLS IT. |
| |
| 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD |
| FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM, |
| NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |