2014-08-12 14:01:32DATE: 8/6/2014
 PROJECT: SUSHI YAMA
 PERMIT#: 14070978
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 107.2.1 PLEASE PROVIDE
 ADDITIONAL DETAIL TO THE PLANS AS FOLLOWS:
  
 2) PROVIDE ALLL CIRCUITRY ON THE FLOOR PLAN AND PANEL
 SCHEDULE, INCLUDE THE EXISTING OUTLETS, AND AS WELL AS
 THE NEW OUTLETS AND DISCONNECTS AS REQUIRED TO MATCH
 THE EQUIPMENT PLAN AS INDICATED ON SHEET 5.
  
 3) PROVIDE POWER RISER DIAGRAM, AND THE LOCATION OF THE
 ELECTRICAL SERVICE ON THE BUILDING.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) PROVIDE LOAD CALCULATIONS ARE REQUIRED FOR THE
 BUILDING ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE
 220. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 7) PROVIDE A LIGHTING PLAN, INDICATE ALL GENERAL
 PURPOSE LIGHTING TASK LIGHTING, SPECIALTY LIGHTING,
 SECURITY LIGHTING, EXIT AND EMERGENCY LIGHTING TO
 COORDINATE WITH THE LIFE SAFETY PLAN.
  
 8) INDICATE LOCATIONS OF CIRCUITRY AND DISCONNECTS FOR
 AIR CONDITIONING AND REFRIGERATION EQUIPMENT.
  
 9) GFI SERVICE OUTLETS REQUIRED FOR MECHANICAL
 EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME
 LEVEL AND WITHIN 25FT OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. SEE NEC 210.63,
 210.8(A)(3), AND 406.8(B)(1),
  
 10) PROVIDE LIGHTING CONTROL. FBC-ENERGY
 A. 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 AUTOMATIC LIGHTING SHUTOFF IS REQUIRED IN BUILDINGS
 LARGER THAN 5,000 SQUARE FEET AND SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS.
  
 B. 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 11) INDICATE THE FIRE SUPRESSION SYSTEM FOR THE KITCHEN
 HOOD. INDICATE HOW THE SYSTEM OPERATES WHAT IS THE
 SEQUESNCE OF EVENTS UPON ACTIVATION. WHAT IT CONTROLS
 AND HOW IT CONTROLS IT.
  
 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: KITCHEN HOOD
 FIRE SUPRESSION, FIRE ALARM, SECURITY, CCTV, DATA/COM,
 NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  