Plan Review Notes For Permit 14070976 |
Permit Number |
14070976 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-11-10 10:28:43 | 1) THE GAS SIZING TABLE FOR THE SCH.40 PIPE IS FROM A | | WEBSITE TITLED "ENGINEERING TOOLBOX." THIS IS NOT A | | RECOGNIZED SIZING METHOD IN ACCORDANCE WITH THE 2010 | | FL. GAS CODE SEC.402.3.SUBMIT A COPY OF THE APPLICABLE | | GAS TABLE FROM THE 2010 FGC. | | 2) SHT.1 OF THE GAS DRAWING SHOWS A 3/4" GALVANIZED | | LINE SUPPLYING THE GAS RANGES AND SHT. 2 SHOWS A 1" AND | | A 1 1/4" WARDFLEX LINE SUPPLYING THE DRYERS. CLARIFY. | | 3) THE MIN. SIZE SCH. 40 PIPE TO SUPPLY BOTH RANGES | | SHALL BE 1 " PER TABLE 402.4 (2). THE MAX. LOAD ON A | | 3/4" PIPE IS 104,000. | | 4) BASED ON THE TOTAL BTU LOAD OF THE SYSTEM, THE MAIN | | GAS LINE FROM THE METER SHALL BE 2" IN ACCORDANCE WITH | | TABLE 402.4 (2) OF THE 2010 FGC. A MAX. OF 532,000 | | BTU'S IS PERMITED ON AN 1 1/2 SCH. 40 LINE. | | 5) INDICATE THE LOCATION OF THE METER ON THE GAS | | DRAWING. | | 6) THE 1 "WARDFLEX LINE SUPPLYING THE LINE TO THE TWO | | RANGES IS UNDERSIZED ACCORDING TO THE WARDFLEX TABLE | | THAT WAS SUBMITTED. | | 7) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2010 | | FGC SEC. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|