Plan Review Notes
Plan Review Notes For Permit 14070976
Permit Number 14070976
Review Stop G
Sequence Number 2
Notes
Date Text
2014-10-20 14:37:351) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLES
 FOR THE PIPE MATERIAL FROM THE 2010 FGC.
 2) SHOW THE TOTAL DISTANCE OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET PER THE 2010 FGC
 SEC.402.4.1.
 3) SHOW THE TOTAL BTU LOAD ON THE SYSTEM. WPB AMEND. TO
 2010 FGC SEC. 107.2.1.
 4)IDENTIFY ALL THE APPLIANCES ON THE GAS DRAWING. WPB
 AMEND. TO 2010 FGC SEC. 107.2.1.
 5) INDICATE THE OPERATING PRESSURE (PSI) OF THE SYSTEM.
 WPB AMEND. TO 2010 FGC SEC. 107.2.1.
 6) SOME OF THE BTU LOADS ARE HARD TO READ.
 7) SHOW THE CORRESPONDING EHD FOR THE DIFFERENT SIZE OF
 THE CSST.
 8) PART OF THE INFO ON THE TOP OF THE GAS PIPING
 DRAWING IS CUT OFF.
 9) DETAILS # 1& #2 - WHAT ARE THE 3/4" CAPPED OFF LINES
 FOR ON THE GAS PIPING DRAWING.
 10) WHAT IS THE 75,000 BTU LOAD SHOWN AT THE TOP OF THE
 PAGE FOR DETAILS #1 & # 2 ? THE PIPING PLAN SHOWS THE
 APPLIANCE AS 150,000 BTU'S.
 11) WHAT TYPE OF APPLIANCE IS DETAIL #1 & DETAIL #2.
 THIS DRAWING IS CONFUSION.
  
  