Plan Review Notes
Plan Review Notes For Permit 14070933
Permit Number 14070933
Review Stop P
Sequence Number 1
Notes
Date Text
2014-07-31 07:40:13PLUMBING PLAN REVIEW
 PERMIT: 14070933
 ADD: 326 FERN ST.
 CONT: STRATICON
 TEL: (561) 436-4733
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 31/ 2014
 ACTION: DENIED
  
 1) SEE BUILDING COMMENTS IN REGUARDS TO OCCUPANCY &
 OCCUPANT LOAD. THIS OCCUPANCY IS TO BE CONSIDERED A
 BUSINESS OCCUPANCY WITH A OCCUPANT LOAD OF 16
 OCCUPANTS, 2010 FBC-B 304.1 & TABLE 1004.1.1.
  
 2) SHEET A2.01 T IS MISSING A DRINKING FOUNTAIN PER
 SECTION 2010 FBC-P TABLE 403.1(2).
  
 3) 2010 FBC-ACCESSIBILITY CODE 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 4) SHEET P0.1 THE SANITARY RISER SHOWS THE USE OF AN
 AIR ADMITTANCE VALVE WITH THE NEW SINK. PLEASE BE AWARE
 THE LIMITATION ON THE USE OF AIR ADMITTANCE VALVES.
 2010 FBC-P WHERE PERMITTED.
 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE
 DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 4) THE NEW SINK DOES NOT INDICATE WHAT THE USAGE OF
 THIS SINK IS FOR, IF IT IS TO BE USED FOR A BREAK ROOM
 SINK IT MUST MEET THE 2010 FL ACCESIBILITY
 REQUIREMENTS: 606.1 GENERAL.
 LAVATORIES AND SINKS SHALL COMPLY WITH 606.1-5.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  