Date |
Text |
2014-07-31 07:40:13 | PLUMBING PLAN REVIEW |
| PERMIT: 14070933 |
| ADD: 326 FERN ST. |
| CONT: STRATICON |
| TEL: (561) 436-4733 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JULY 31/ 2014 |
| ACTION: DENIED |
| |
| 1) SEE BUILDING COMMENTS IN REGUARDS TO OCCUPANCY & |
| OCCUPANT LOAD. THIS OCCUPANCY IS TO BE CONSIDERED A |
| BUSINESS OCCUPANCY WITH A OCCUPANT LOAD OF 16 |
| OCCUPANTS, 2010 FBC-B 304.1 & TABLE 1004.1.1. |
| |
| 2) SHEET A2.01 T IS MISSING A DRINKING FOUNTAIN PER |
| SECTION 2010 FBC-P TABLE 403.1(2). |
| |
| 3) 2010 FBC-ACCESSIBILITY CODE 211.2 MINIMUM NUMBER. NO |
| FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| 4) SHEET P0.1 THE SANITARY RISER SHOWS THE USE OF AN |
| AIR ADMITTANCE VALVE WITH THE NEW SINK. PLEASE BE AWARE |
| THE LIMITATION ON THE USE OF AIR ADMITTANCE VALVES. |
| 2010 FBC-P WHERE PERMITTED. |
| 917.3.1 LOCATION OF BRANCH. |
| THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE |
| DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| 917.3.2 RELIEF VENT. |
| WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR |
| BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR |
| EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL |
| CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE |
| STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED |
| TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL |
| BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED |
| IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL |
| BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |
| |
| 4) THE NEW SINK DOES NOT INDICATE WHAT THE USAGE OF |
| THIS SINK IS FOR, IF IT IS TO BE USED FOR A BREAK ROOM |
| SINK IT MUST MEET THE 2010 FL ACCESIBILITY |
| REQUIREMENTS: 606.1 GENERAL. |
| LAVATORIES AND SINKS SHALL COMPLY WITH 606.1-5. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |