Plan Review Notes For Permit 14070933 |
Permit Number |
14070933 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-26 10:40:45 | DATE: 8/26/2014 | | PROJECT: 333 DOWNTOWN SALES OFFICE | | PERMIT#: 14070933 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) ONLY ONE COPY OF THE "E" SHEETS FOR THE ELECTRICAL | | REVIEW WERE SUBMITTED WITH THE SUBMITTAL PACKAGE. THE | | INITIAL REVIEW APPEARS TO BE CODE COMPLIANT AND COULD | | PASS WITH THE SUBMUITTAL OF THE SECOND SET OF | | ELECTRICAL SHEETS. MISSING ONE SET E0.1, E1.1, E2.1, | | E3.1 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | ITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|