2014-08-22 11:12:27 | | | 14070924 | | 222 LAKEVIEW AVE. #1700 | | TENANT IMPROVEMENT | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN | | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; | | 505.5.3; T. 505.5.3 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | DISCONNECTING MEANS. NEC 110.16, 110.22 | | | | SHOW ALL EXISTING FEEDERS WITH WIRE AND CONDUIT SIZE. | | PROVIDE THE WIRE AND CONDUIT SIZE PROPOSED FOR THE | | RELOCATED PANELS. SHOW THE LOCATION OF THE SECONDARY | | OVER CURRENT PROTECTION REQUIRED AT THE TRANSFORMER FOR | | THE FEEDER AND THE PANEL BOARDS. THE RISER PLAN AND THE | | PANEL BOARD SCHEDULES DO NOT SEEM TO MATCH. NEC 215.5, | | 240.4, 240.21, 240.21(C) | | | | PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR | | PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | [email protected] | | | | |
|