Plan Review Notes
Plan Review Notes For Permit 14070876
Permit Number 14070876
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-28 08:01:002010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE SITE PLAN INDICATES THAT THE WATER'S EDGE OF THE
 POOL IS 7'-3" HORIZONTALLY TO THE OVERHEAD POWER LINES.
 SHOW COMPLIANCE WITH NEC 680.8 FOR OVERHEAD CONDUCTOR
 CLEARANCES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714