Plan Review Notes For Permit 14070836 |
Permit Number |
14070836 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-24 09:47:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE PROPOSED MAIN ENTRANCE DOOR IS SHOWN TO BE SWINGING | | INTO THE EXISTING EXIT CORRIDOR AND ENCROACHES ON AND | | RESTRICTS EXITING ALONG THE CORRIDOR. THE MAIN ENTRANCE | | DOOR SHALL SWING INTO THE OFFICE SPACE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | |
|