Date |
Text |
2014-08-22 16:53:41 | DATE: 8/22/2014 |
| PROJECT: THE VITAMIN SHOPPE |
| PERMIT#: 14070794 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| DUPLICATE COMMENTS NOT ADDRESSED ON RE-SUBMITTAL. |
| |
| 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 THE |
| DESIGN PROFESSIONAL IS REQUIRED TO SIGN THE PLANS. |
| |
| 2) IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. FBC |
| WPB AMENDMENTS. SECTION 109.3 |
| PROVIDE SUPPORTING DOCUMENTATION FOR THE VALUATION OF |
| THE PROJECT AS INDICATED ON THE PERMIT APPLICATION. THE |
| VALUE SHALL INCLUDE ALL ENGINEERING, PARTS, LABOR, |
| OVERGEAD AND PROFIT. |
| |
| 4) NEC 600.7(1) SIGNS AND METAL EQUIPMENT OF OUTLINE |
| LIGHTING SYSTEMS SHALL BE GROUNDED BY CONNECTION TO THE |
| EQUIPMENT GROUNDING CONDUCTOR OF THE SUPPLY BRANCH |
| CIRCUIT(S) OR FEEDER USING THE TYPES OF EQUIPMENT |
| GROUNDING CONDUCTORS SPECIFIED IN THE NEC 250.118. |
| PROVIDE AND INDICATE ON THE PLANS THAT AN EQUIPMENT |
| GROUNDING CONDUCTOR WILL BE ROUTED WITH THE SUPPLY |
| CONDUCTORS AND SIZRED IN ACCORDANCE WITH THE NEC |
| 250.118 FOR CONNECTION TO THE SIGN AS REQUIRED BY NEC |
| 600.7 AS INDICATED ABOVE. |
| |
| 5) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| 505.2.4 |
| PROVIDE AND INDICATE ON THE PLANS HOW THE SIGN CIRCUIT |
| WILL BE CONTROLLED IN ORDER TO MEET THE INTENT OF THE |
| FBC-E SECTION 505.2.4 AS INDICATED ABOVE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |