2014-08-02 14:41:40DATE: 8/2/2014
 PROJECT: THE VITAMIN SHOPPE
 PERMIT#: 14070794
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 THE
 DESIGN PROFESSIONAL IS REQUIRED TO SIGN THE PLANS.
  
 2) IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. FBC
 WPB AMENDMENTS. SECTION 109.3
  
 3) 600.4 MARKINGS.
 (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND
 OUTLINELIGHTING SYSTEMS SHALL BE MARKED WITH THE
 MANUFACTURER?SNAME, TRADEMARK, OR OTHER MEANS OF
 IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
 (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS.
 SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR
 INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE
 MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE
 MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT
 LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE
 VISIBLE DURING RELAMPING.
 (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO
 INDICATE THAT FIELD-WIRING AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED.
 NEC 110.3 LISTING AND LABELING REQUIRED BY AN APPROVED
 TESTING LAB. IN JUDGING EQUIPMENT, CONSIDERATION SUCH
 AS THE FOLLOWING SHALL BE EVALUATED: SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. NEC 110.3(A)(1 THRU 8)
  
 4) NEC 600.7(1) SIGNS AND METAL EQUIPMENT OF OUTLINE
 LIGHTING SYSTEMS SHALL BE GROUNDED BY CONNECTION TO THE
 EQUIPMENT GROUNDING CONDUCTOR OF THE SUPPLY BRANCH
 CIRCUIT(S) OR FEEDER USING THE TYPES OF EQUIPMENT
 GROUNDING CONDUCTORS SPECIFIED IN THE NEC 250.118.
 PROVIDE AND INDICATE ON THE PLANS THAT AN EQUIPMENT
 GROUNDING CONDUCTOR WILL BE ROUTED WITH THE SUPPLY
 CONDUCTORS AND SIZRED IN ACCORDANCE WITH THE NEC
 250.118 FOR CONNECTION TO THE SIGN AS REQUIRED BY NEC
 600.7 AS INDICATED ABOVE.
  
 5) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
 PROVIDE AND INDICATE ON THE PLANS HOW THE SIGN CIRCUIT
 WILL BE CONTROLLED IN ORDER TO MEET THE INTENT OF THE
 FBC-E SECTION 505.2.4 AS INDICATED ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]