Notes |
Date |
Text |
2014-07-25 12:13:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | ON SHEET A-2 IN THE FLOOR PLAN NOTES SECTION IT READS | | "ALL NEW DOORS SHALL BE IN FULL COMPLIANCE WITH THE | | PROVISIONS OF NFPA 101, 24.2.4". THAT SECTION OF THE | | CODE REFERS TO ONE AND TWO FAMILY DWELLINGS AND IS NOT | | APPLICCABLE TO THIS OCCUPANCY. A PROVISO HAS BEEN ADDED | | TO READ "37.2.2.2", REFERING TO MERCANTILE OCCUPANCY. | | | | ON SHEET A-2 IN THE FLOOR PLAN DRAWING, IT READS NEW | | IMPACT RATED DOOR WITH SECURITY SHUTTER ON INSIDE. THE | | SHUTTER SHALL NOT RESTRICT EGRESS AND COMPLY WITH NFPA | | 101, CHAPTER 7. THE FIRE INSPECTOR SHALL CONFIRM | | COMPLIANCE ON FINAL INSPECTION. |
|