Plan Review Notes
Plan Review Notes For Permit 14070650
Permit Number 14070650
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-24 07:49:39BUILDING PLAN REVIEW
 PERMIT: 14070650
 ADD: 1101 N TAMARIND AVE.
 CONT: FASTRACK CONSTRUCTION
 TEL: (561)772-8848
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 24/ 2014
 ACTION: DENIED
  
 1) SHEET A2 INDICATES A 2'-9" ACCESSIBLE RAMP WITH
 DETECTABLE WARNING ON THE RAMP. THE RAMP IS LACKING A
 TOP LANDING IN THE DIRECTION OF TRAVEL WITHOUT HAVING
 TO MAKE A 90 DEGREE TURN. PLEASE REVIEW THE FOLLOWING
 2010 FL ACCESSIBILITY CODE SECTIONS THAT DEAL WITH
 RAMPS.
 1A) 405.3 CROSS SLOPE. CROSS SLOPE OF RAMP RUNS SHALL
 NOT BE STEEPER THAN 1:48.
  
 1B) 405.4 FLOOR OR GROUND SURFACES. FLOOR OR GROUND
 SURFACES OF RAMP RUNS SHALL COMPLY WITH 302. CHANGES IN
 LEVEL OTHER THAN THE RUNNING SLOPE AND CROSS SLOPE ARE
 NOT PERMITTED ON RAMP RUNS.
  
 1C) 405.7 LANDINGS. RAMPS SHALL HAVE LANDINGS AT THE
 TOP AND THE BOTTOM OF EACH RAMP RUN. LANDINGS SHALL
 COMPLY WITH 405.7.
  
 1D) 05.7.3 LENGTH. THE LANDING CLEAR LENGTH SHALL BE 60
 INCHES (1525 MM) LONG MINIMUM.
  
 1E) 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 2) THE EXITING RESTROOM IS NOT CODE COMPLIANT TO THE
 2010 FL ACCESSIBILITY CODE, PLEASE REVIEW 2010 FL
 ACCESSIBILITY CODE 604.3.2.NOR DOES THE PLANS SHOW ANY
 ELEMENTS FOR A ACCESSIBLE RESTROOM.
  
 3) SUBMITTED PRODUCT APPROVAL FOR EXTERIOR DOORS IS NOA
 12-0706.03 PLEASE SHOW (CIRCLE) WHICH THRESHOLD WILL BE
 INSTALLED PAGE 2.1 OF 7 TO MAKE THE BUILDING CODE
 COMPLIANT WITH 2010 FL ACCESSIBILITY CODE 404.2.5.
  
 4) PLEASE REVIEW 2010 FL ACCESSIBILITY CODE, SECTIONS
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE MAKE A ITEMIZED LIST WHERE $25,000.00 DOLLARS OF
 ACCESSIBLE UPGRADES (20%) WILL BE MADE TO MAKE THE
 BUILDING ACCESSIBLE TO THE CURRENT 2010 ACCESSIBILITY
 CODE.
  
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) NOTE AWNING SHOWN ON THE PLANS WILL BE REVIEWED
 UNDER A SEPARATE PERMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  