2014-07-24 09:27:57 | DATE: 7/24/2014 | | PROJECT: PBOM W407-W408 | | PERMIT#: 14070606 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION | | 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE | | A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE | | INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL | | NOT BE REDUCED. FBC 713.3.2 MEMBRANE PENETRATIONS. BACK | | TO BACK ELECTRICAL BOXES SHALL BE INSTALLED IN | | COMPLIANCE WITH THIS ARTICLE. | | | | 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G) | | | | 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | 110.16, 110.22 | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|