2014-07-24 09:27:57DATE: 7/24/2014
 PROJECT: PBOM W407-W408
 PERMIT#: 14070606
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION
 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE
 A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. FBC 713.3.2 MEMBRANE PENETRATIONS. BACK
 TO BACK ELECTRICAL BOXES SHALL BE INSTALLED IN
 COMPLIANCE WITH THIS ARTICLE.
  
 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G)
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]