2014-11-07 09:10:401) THE SANITARY IS NOT DRAWN TO CODE. SUBMIT A
 COMPLETELY NEW CODE COMPLIANT RISER DIAGRAM FOR REVIEW
 . WPB AMEND. TO 2010 FBC SEC.107.3.5.3.
 2) 2010 FBCR SEC. P3104.3 - EVERY DRY VENT CONNECTING
 TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. A FLAT DRY
 VENT IS NOT PERMITTED.
 3) THE PLUMBING FIXTURES SHALL BE VENTED PER THE 2010
 FBCR SEC.P3101.2, P3101.2.1.
 4) CLEANOUTS ARE REQUIRED IN ALL STACKS. 2010 FBCR
 SEC.P3005.2.6.
 5) A CLEANOUT IS REQUIRED AT THE BUILDING DRAIN AND
 BUILDING SEWER PER THE 2010 FBCR SEC.P3005.2.7.
  