2014-11-06 08:30:24PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 THE ENERGY CALCULATION FORM CONTAINS SOME DISCREPANCIES
 THAT NEED TO BE CORRECTED.
 1) FOR ITEM #3 THE NUMBER OF UNITS SHOULD BE 2. FBC
 107.2.1
 2) THE EQUIPMENT SIZING CALCULATIONS HAVE A TOTAL
 COOLING LOAD OF 17,198 BTUH. FBC ENERGY CONSERVATION
 SECTION 403.6.1.1 STATES THAT THE COOLING EQUIPMENT CAN
 NOT BE MORE THAN 1.15 TIMES GREATER THAN THE TOTAL
 CALCULATED LOAD. THE 24,000 BTU/HR SPECIFIED ON THE
 ENERGY FORM IS MORE THAN 1.15 TIMES 17,198 BTUH.
 THEREFORE, ITEM #12 SHOULD BE 18 BTUH.
 3) THE FORM SPECIFIES A 16.00 SEER FOR THE COOLING
 EQUIPMENT AND THE PAPERWORK THAT WAS SUBMITTED FOR THE
 GOODMAN EQUIPMENT INDICATES THAT IT HAS A SEER OF
 13.00. PLEASE CORRECT. FBC 107.2.1